“C” Group: Intelligent Terminal Functions
Configur
ing Dr
iv
e
P
a
ra
meters
3–50
“C” Group: Intelligent Terminal Functions
The eight input terminals [
1]
, [
2]
, [
3]
, [
4]
, [
5]
, [
6]
, [
7],
and [
8]
can be configured for any of 44
different functions. The next two tables show how to configure the eight terminals. The inputs
are logical, in that they are either OFF or ON. We define these states as OFF=0, and ON=1.
The inverter comes with default options for the eight terminals. These default settings are
initially unique, each one having its own setting. Note that European and US versions have
different default settings. You can use any option on any terminal, and even use the same option
twice to create a logical OR (though usually not required).
Input Terminal
Configuration
Functions and Options
–The
function codes
in the following table let you assign one of 44
options to any of the eight logic inputs for the SJ700
2
inverters. The functions C001 through
C008 configure the terminals [1] through [8] respectively. The “value” of these particular
parameters is not a scalar value, but it is a discrete number that selects one option from many
available
options
.
For example, if you set function C001=01, you have assigned option 01 (Reverse Run) to
terminal [1]. The option codes and the specifics of how each one works are in Chapter 4.
The input logic convention is programmable for each of the six inputs. Most inputs default to
normally open (active high), but you can select normally closed (active low) in order to invert
the sense of the logic.
Func.
Code
Name/
Description
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
FEF2
FE2
(EU)
FUF2
FU2
(USA)
FF2
F2
(Jpn)
C001
Terminal [1] function
63 programmable functions
available for terminals (see
next section)
18 [RS]
18 [RS]
18 [RS]
✘ ✔
C002
Terminal [2] function
16 [AT]
16 [AT]
16 [AT]
✘ ✔
C003
Terminal [3] function
06 [JG]
06 [JG]
06 [JG]
✘ ✔
C004
Terminal [4] function
11 [FRS]
11 [FRS]
11 [FRS]
✘ ✔
C005
Terminal [5] function
09 [2CH]
09 [2CH]
09 [2CH]
✘ ✔
C006
Terminal [6] function
03 [CF2]
13 [USP]
03 [CF2]
✘ ✔
C007
Terminal [7] function
02 [CF1]
02 [CF1]
02 [CF1]
✘ ✔
C008
Terminal [8] function
01 [RV]
01 [RV]
01 [RV]
✘ ✔
Func.
Code
Name/
Description
Keypad
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
SRW
OPE
FEF2
FE2
(EU)
FUF2
FU2
(USA)
FF2
F2
(Jpn)
C011
Terminal [1] active state
NO
00
Normally open (N.O.)
00
00
00
✘ ✔
NC
0 1
Normally closed (N.C.)
✘ ✔
C012
Terminal [2] active state
NO
00
Normally open (N.O.)
00
00
00
✘ ✔
NC
0 1
Normally closed (N.C.)
✘ ✔
C013
Terminal [3] active state
NO
00
Normally open (N.O.)
00
00
00
✘ ✔
NC
0 1
Normally closed (N.C.)
✘ ✔
C014
Terminal [4] active state
NO
00
Normally open (N.O.)
00
00
00
✘ ✔
NC
0 1
Normally closed (N.C.)
✘ ✔