SJ700
2
Inverter
Configur
ing Dr
iv
e
P
a
ra
met
e
rs
3–7
D012
Torque monitor
Estimated output torque value, range is -300.0
to +300.0%
%
D013
Output voltage monitor
Voltage of output to motor,
range is 0.0 to 600.0V
VAC
D014
Power monitor
Input power to inverter, range is 0.0 to 999.9
kW
D015
Cumulative power monitor
Displays cumulative input power to inverter;
B079 selects the multiplier for units. Range is
0.0 to 999.9, 1000 to 9999, or 100 to 999
kW/h
D016
Cumulative operation RUN
time monitor
Displays total time the inverter has been in
RUN mode in hours.
Range is 0 to 9999 / 1000 to 9999/
100 to 999 (10,000 to 99,900) hrs.
hours
D017
Cumulative power-on time
monitor
Displays total time the inverter has had input
power (ON) in hours. Range is:
0 to 9999 / 100.0 to 999.9 /
1000 to 9999 / 100 to 999 hrs.
hours
D018
Heat sink temperature
monitor
Displays the temperature of the inverter’s heat
sink
°C
D019
Motor temperature monitor
Displays motor internal temperature (requires
an NTC thermistor installed in the motor and
connected to [TH] and [CM1]).
°C
D022
Component life monitor
Displays estimated life status of DC bus
capacitors and cooling fans
—
D023
Program counter
Displays the current program step being
executed when the inverter is operating under
the control of an EZ Sequence program
Programs
D024
Program number counter
Displays the EZ Sequence program identifica-
tion number, if defined in the program, when a
program is loaded in the inverter
Program
D025
User monitor 0
Displays state of internal EZ Sequence register
User Monitor 0
—
D026
User monitor 1
Displays state of internal EZ Sequence register
User Monitor 1
—
D027
User monitor 2
Displays state of internal EZ Sequence register
User Monitor 2
—
D028
Pulse counter
Displays accumulated pulse count of [PCNT]
intelligent input terminal (option code 74)
Pulses
D029
Position setting monitor
Displays absolute position command for
motor shaft in absolute position control mode
Pulses
D030
Position feedback monitor
Displays absolute position of motor shaft
when in absolute position control mode
Pulses
D102
DC voltage monitoring
Displays the DC Bus voltage
V
D103
BRD load factor monitoring
Displays the running average Dynamic
Braking usage ratio (%ED)
%
D104
Electronic thermal overload
monitoring
Displays the motor electronic thermal
overload estimated temperature ratio. If the
value reaches 100%, the inverter will trip
(E05).
%
Func.
Code
Name
Description
Units