The miscellaneous settings include scaling factors, initialization modes, and others. This
section covers some of the most important settings you may need to configure.
Function Display
Settings
The inverter has the (optional) capability to suppress the display and editing of certain parame-
ters. Use B037 to select the display options. The purpose of this feature is to hide particular
secondary parameters that become unused or not applicable based on more fundamental param-
eter settings. For example, setting A001 = 01 configures the inverter to get its frequency
command from the front keypad potentiometer. In this case, the inverter will not use the analog
inputs nor their adjustment parameters for an external frequency command.
For example, you can set B037=01 to have the inverter suppress the displaying of all analog
input parameters when A001=01, as shown in the first row of the following table.
Func.
Code
Name/
Description
Keypad
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
SRW
OPE
FEF2
FE2
(EU)
FUF2
FU2
(USA)
FF2
F2
(Jpn)
B034
Run/power-on warning time
—
—
0 to 9999. (0 to 99990), 1000 to
6553 (10000 to 655300) (hours)
0.
0.
0.
✘ ✔
B035
Rotational direction restriction
FREE
00
Enable for both directions
00
00
00
✘ ✘
FW
0 1
Enable for forward only
✘ ✘
RV
02
Enable for reverse only
✘ ✘
B036
Reduced voltage start selection
—
—
000 (short) to 255 (long)
06
06
06
✘ ✔
Func.
Code
Name/
Description
Keypad
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
SRW
OPE
xFE2
(EU)
xFU2
(USA)
xFF2
(Jpn)
B037
Function code display
restriction
ALL
00
Display all
04
04
04
✘ ✔
FUNCTION
0 1
Display only utilized functions (see
table on next page)
USER
02
Display user-selected functions only
(configure with U01 to U12)
COMPARE
03
Data comparison display
BASIC
04
Basic display
B038
Initial display selection
STR
00
Last value dislayed when STR key
was pressed
01
01
01
✘ ✔
FM
0 1
D001
Iout
02
D002
Dir
03
D003
F-CNV
04
D007
F-SET
05
F001
B039
Automatic user parame-
ter function enable
OFF
00
Disable
00
00
00
✘ ✔
ON
0 1
Enable
Function
Code
Data
Resulting Non-displayed
Functions (when B37 = 01)
Notes
A001
01
A005, A006, A011 – A016, A101 –
A114, C081 – C083, C121 – C123
[O], [OI], [O2] terminal
functions