occurred, the inverter and motor will enter free-run stop (coasting) operation. In some applica-
tions, the motor and load will still be coasting when the inverter returns to normal Run Mode
operation. For that situation, you can configure the inverter output (C103=00) to resume opera-
tion from 0 Hz and accelerate normally. Or, you can configure the inverter (C103=01) to
resume operation from the current speed of the motor (
frequency matching
)—often used in
applications such as HVAC.
Output Terminal
Signal Functions
Func.
Code
Name/
Description
Keypad
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
SRW
OPE
xFE2
(EU)
xFU2
(USA)
xFF2
(Jpn)
C102
Reset mode selection
ON
00
Cancel trip state, stop inverter output, reset
CPU; clear position counter at ON transition
00
00
00
✔ ✔
Determines response to
Reset input [RST]
OFF
0 1
Cancel trip state, stop inverter output, reset
CPU; clear position counter at OFF transi-
tion
TRP
02
Cancel trip state and clear position counter;
no effect if a trip does not exist
EXT
03
Cancel trip state but does not clear position
counter; no effect if a trip does not exist
C103
Restart mode after reset
ZST
00
Restart at 0 Hz
00
00
00
✘ ✔
fST
0 1
Resume operation after frequency matching
FIX
02
Restart with active matching frequency
C105
FM gain adjustment
50. to 200. (%)
100.
100.
100.
✘ ✔
C106
AM gain adjustment
50. to 200. (%)
100.
100.
100.
✘ ✔
C107
AMI gain adjustment
50. to 200. (%)
100.
100.
100.
✔ ✔
C109
AM bias adjustment
0. to 100. (%)
0.
0.
0.
✔ ✔
C110
AMI bias adjustment
0. to 100. (%)
20.
20.
20.
✔ ✔
C111
Overload setting (2)
0.00 x rated current to 1.80 x rated current
(A)
Rated current for
inverter
✘ ✔
Func.
Code
Name/
Description
Keypad
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
SRW
OPE
FEF2
FE2
(EU)
FUF2
FU2
(USA)
FF2
F2
(Jpn)
C130
Terminal [11] ON-delay time
—
—
0.0 to 100.0 (seconds)
0.0
0.0
0.0
✘ ✔
C131
Terminal [11] OFF-delay time
—
—
0.0 to 100.0 (seconds)
0.0
0.0
0.0
✘ ✔
C132
Terminal [12] ON-delay time
—
—
0.0 to 100.0 (seconds)
0.0
0.0
0.0
✘ ✔
C133
Terminal [12] OFF-delay time
—
—
0.0 to 100.0 (seconds)
0.0
0.0
0.0
✘ ✔
C134
Terminal [13] ON-delay time
—
—
0.0 to 100.0 (seconds)
0.0
0.0
0.0
✘ ✔
C135
Terminal [13] OFF-delay time
—
—
0.0 to 100.0 (seconds)
0.0
0.0
0.0
✘ ✔
C136
Terminal [14] ON-delay time
—
—
0.0 to 100.0 (seconds)
0.0
0.0
0.0
✘ ✔
C137
Terminal [14] OFF-delay time
—
—
0.0 to 100.0 (seconds)
0.0
0.0
0.0
✘ ✔
C138
Terminal [15] ON-delay time
—
—
0.0 to 100.0 (seconds)
0.0
0.0
0.0
✘ ✔