Appendix B
B–15
Command – 07
The 07 command sets a parameter value equal to the value specified in the transmission. The
frame format of command 07 follows the diagram and specification table.
Note that the parameter F001, the output frequency, can be set more directly with host
command 01 instead of with this command. Use the codes in the following table for setting
parameters associated with H003 and H203.
Element
Description
Size
Value
STX
Control code (STart of TeXt)
1 byte
STX (0x02)
Node
Node (station) address of inverter
2 bytes 01 to 32, and FF (broadcast to all
nodes)
Command
Transmission command
2 bytes 07
Parameter
Function code of parameter
4 bytes F002..., A001..., B001..., C001...,
H003..., P001...
Data
Transmission data
8 bytes Value of parameter times ten as
ASCII char. code, except for
H003 and H203 (see table below)
BCC
Block check sum code
2 bytes Exclusive OR of Node,
Command, and Data
[CR]
Control code (carriage return)
1 byte
[CR] (0x0D)
STX Node
Command
Data
BCC [CR]
Frame format
Parameter
Code Data
00
01
02
03
04
05
06
07
08
09
10
Japan or U.S.A. mode (B85 = 00 or 02)
0.2 kW
—
0.4
—
0.75
—
1.5
2.2
—
3.7
—
EU mode (B85=01)
0.2 kW
0.37
—
0.55
0.75
1.1
1.5
2.2
3.0
—
4.0
Code Data
11
12
13
14
15
16
17
18
19
20
21
Japan or U.S.A. mode (B85 = 00 or 02)
5.5 kW
7.5
11
15
18.5
22
30
37
45
55
75
EU mode (B85=01)
5.5 kW
7.5
11
15
18.5
22
30
37
45
55
75
Code Data
22
23
24
25
26
27
28
29
30
31
32
Japan or U.S.A. mode (B85 = 00 or 02)
90 kW
110
132
150
160
185
200
220
250
280
300
EU mode (B85=01)
90 kW
110
132
150
160
185
200
220
250
280
300
Code Data
33
34
35
36
—
—
—
—
—
—
—
Japan or U.S.A. mode (B85 = 00 or 02) 315 kW
340
355
400
—
—
—
—
—
—
—
EU mode (B85=01)
315 kW
340
355
400
—
—
—
—
—
—
—