ModBus Data Listing
Append
ix
B
B–34
Note 1:
ON usually when either the control circuit terminal board or a coil is ON. Among
intelligent input terminals, the control circuit terminal board is a high-priority termi-
nal. If the master cannot reset the coil ON status due to a transmission line break, turn
ON and OFF the control circuit terminal board to make the coil OFF status.
0018h
00024
AL - Alarm signal
R
0... OFF
1... ON
0019h
00025
FA3 - Frequency arrival signal
(set frequency or above)
R
001Ah
00026
OTQ - Over-torque
R
001Bh
00027
IP - Instantaneous power failure
R
001Ch
00028
UV - Uundervoltage
R
001Dh
00029
TRQ - Torque limit
R
001Eh
00030
RNT - Operation time over
R
001Fh
00031
ONT - Plug-in time over
R
0020h
00032
THM - Thermal alarm signal
R
0021h
00033
(Reserved)
—
—
0022h
00034
(Reserved)
—
—
0023h
00035
(Reserved)
—
—
0024h
00036
(Reserved)
—
—
0025h
00037
(Reserved)
—
—
0026h
00038
BRK - Brake release
R
0... OFF
1... ON
0027h
00039
BER - Brake error
R
0028h
00040
ZS - 0 Hz detection signal
R
0029h
00041
DSE - Speed deviation
maximum
R
002Ah
00042
POK - Positioning completed
R
002Bh
00043
FA4 - Set frequency
overreached 2
R
002Ch
00044
FA5 - Set frequency reached 2
R
002Dh
00045
OL2 - Overload notice advance
signal 2
R
002Eh
00046
Odc - Analog O disconnection
detection
R
002Fh
00047
OIDc - Analog OI
disconnection detection
R
0030h
00048
O2Dc - Analog O2
disconnection detection
R
0031h
00049
(Reserved)
—
—
0032h
00050
FBV - PID feedback
comparison
R
0... OFF
1... ON
0033h
00051
NDc - Communication bus
disconnection
R
0034h
00052
LOG1 - Logical operation
result 1
R
List of Coil Numbers
Coil number
Name
R/W
Description
hex
dec.