ModBus Data Listing
Append
ix
B
B–52
A145
H ADD frequency
R/W
0.00 to 99.99,
100.0 to 400.0 (Hz)
12B3h
04787
0 to 40000
0.01 Hz
A145
L
R/W
12B4h
04788
A146
— ADD direction select
R/W
00..Plus (adds A145 value to
output frequency)
01..Minus (subtracts A145
value from output freq.)
12B5h
04789
0, 1
—
—
(Reserved)
—
—
12B6h
to
12B8h
04790t
o
04792
—
—
A150
— EL-S curve acceleration
ratio 1
R/W
Range is 0. to 50.
12B9h
04793
0 to 50
1 %
A151
— EL-S curve acceleration
ratio 2
R/W
Range is 0. to 50.
12BAh
04794
0 to 50
1 %
A152
— EL-S curve acceleration
ratio 3
R/W
Range is 0. to 50.
12BBh
04795
0 to 50
1 %
A153
— EL-S curve acceleration
ratio 4
R/W
Range is 0. to 50.
12BCh
04796
0 to 50
1 %
—
(Reserved)
—
—
12BDh
to
1300h
04797
to
04864
—
—
Holding Registers, “A” Group Standard Functions
Func. Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.
Holding Registers, “B” Group Fine Tuning Functions
Func. Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.
B001
— Selection of restart mode
R/W
00 . Alarm output after trip,
automatic restart disabled
01 . Resume operation after
frequency matching
02 . Resume operation after
frequency matching
03 . Resume previous freq.
after freq. matching, then
decelerate to stop and
display trip info
04 . Restart with active
matching frequency
1301h
04865
0 to 4
—
B002
— Allowable under-voltage
power failure time
R/W
The amount of time a power
input under-voltage can occur
without tripping the power
failure alarm
1302h
04866
3 to 250
0.1 sec.