SJ700
2
Inverter
Appendix B
B–63
C085
— Thermistor input tuning
R/W
0.0 to 999.9., 1000
1459h
05209
—
(Reserved)
—
—
145Ah
to
145Eh
05210
to
05214
—
—
C091
— Debug mode enable
R
00 . No display
01 . Display
145Fh
05215
0, 1
—
—
— (Reserved)
—
—
1460h
to
1468h
05216
to
05224
—
—
C101
— Up/Down memory mode
selection
R/W
00 . Clear last freq. (return to
default freq. F001)
01 . Keep last frequency
adjusted by UP/DWN
1469h
05225
0, 1
—
C102
— Reset mode selection
R/W
00 . Cancel trip state, stop
inverter output, reset CPU;
clear position counter at ON
transition
01 . Cancel trip state, stop
inverter output, reset CPU;
clear position counter at OFF
transition
02 . Cancel trip state and
clear position counter; no
effect if a trip does not exist
03 . Cancel trip state but does
not clear position counter; no
effect if a trip does not exist
146Ah
05226
0 to 3
—
C103
— Restart mode after reset
R/W
00 . Restart at 0 Hz
01 . Resume operation after
frequency matching
02 . Restart with active
matching frequency
146Bh
05227
—
(Reserved)
—
—
146Ch
05228
—
—
C105
— FM gain adjustment
R/W
50. to 200. (%)
146Dh
05229
50 to 200
1 %
C106
— AM gain adjustment
R/W
50. to 200. (%)
146Eh
05230
50 to 200
1 %
C107
— AMI gain adjustment
R/W
50. to 200. (%)
146Fh
05231
50 to 200
1 %
—
(Reserved)
—
—
1470h
05232
—
—
C109
— AM bias adjustment
R/W
0. to 100. (%)
1471h
05233
0 to 100
1 %
C110
— AMI bias adjustment
R/W
0. to 100. (%)
1472h
05234
0 to 100
1 %
C111
— Overload setting (2)
R/W
0.00 x rated current to
2.00 x rated current (A)
1473h
05235
0 to 1800
0.1 %
—
(Reserved)
—
—
1474h
to
147Ch
05236
to
05244
—
—
C121
— [O] input zero calibration
R/W
0. to 9999., 1000 to 6553
(10000 to 65530)
147Dh
05245
0 to 65530
1
C122
— [OI] input zero calibration
R/W
0. to 9999., 1000 to 6553
(10000 to 65530)
147Eh
05246
0 to 65530
1
Holding Registers, “C” Group Intelligent Terminal Functions
Func. Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.