“H” Group: Motor Constants Functions
Introduction
The “H” Group parameters configure the
inverter for the motor characteristics. You
must manually set H003 and H004 values
to match the motor. Most of the remaining
parameters are related to vector control, and
are in use only when function A044 is set
for one of the vector control modes as
shown in the diagram. The procedure
in
“Auto-tuning of Motor Constants” on
page 4–71
automatically sets all the param-
eters related to vector control. If you
configure the inverter to use vector control,
we highly recommend letting the auto-
tuning procedure derive the values for you.
If you want to reset the parameters to the
factory default settings, use the procedure
in
“Restoring Factory Default Settings” on
page 6–16
.
NOTE:
The auto-tuning procedure and related warning messages are in
“Auto-tuning of Motor
Constants” on page 4–71
. Please read these before trying to auto-tune the motor parameters.
Output
V/f control,
constant torque
V/f control,
variable torque
V/f control, free-
setting curve
Inverter Torque Control Algorithms
Sensorless vector
(SLV) control
Sensorless vector,
0Hz domain
Vector control with
sensor
00
05
04
03
02
01
A044
Func.
Code
Name/
Description
Keypad
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
SRW
OPE
FEF2
FE2
(EU)
FUF2
FU2
(USA)
FF2
F2
(Jpn)
H001
Auto-tuning Setting
NOR
00
Auto-tuning OFF
00
00
00
✘ ✘
NRT
0 1
Auto-tune (measure motor resistance and
inductance, without rotating)
AUT
02
Auto-tune (rotate motor)
H002
Motor data selection, 1st
motor
NOR
00
Standard motor data
00
00
00
✘ ✘
AUT
0 1
Auto-tuning data
ON-
AUT
02
Adaptive tuning data
H202
Motor data selection, 2nd
motor
NOR
00
Standard motor data
00
00
00
✘ ✘
AUT
0 1
Auto-tuning data
ON-
AUT
02
Adaptive tuning data
H003
Motor capacity, 1st motor
0.20 to 400. (kW)
Factory set
✘ ✘
H203
Motor capacity, 2nd motor
0.20 to 400 (kW)
Factory set
✘ ✘
H004
Motor poles setting, 1st motor
2, 4, 6, 8, 10 (poles)
4
4
4
✘ ✘
H204
Motor poles setting, 2nd motor
2, 4, 6, 8, 10 (poles)
4
4
4
✘ ✘