ModBus Data Listing
Append
ix
B
B–36
D001
H Output frequency monitor
R
Real-time display of output
frequency to motor,
from 0.0 to 400.0 Hz
1001h
04097
0 to 40000
0.01 Hz
D001 L
R
1002h
04098
D002
— Output current monitor
R
Filtered display of output current
to motor (100 mS internal filter
time constant)
1003h
04099
0 to 9999
0.01 A
D003
— Rotation direction monitor
R
0 ...Stop
1 ...Forward
2 ...Reverse
1004h
04100
0, 1, 2
—
D004
H Process variable (PV), PID
feedback monitor
R
Displays the scaled PID process
variable (feedback) value (A75 is
scale factor)
1005h
04101
0 to 9990
0.1
D004
L
R
1006h
04102
D005
— Intelligent input terminal
status
R
Displays the state of the intelli-
gent input terminals
1007h
04103
bit 0 = [1] bit
7= [8] termi-
nals
1 bit
D006
— Intelligent output terminal
status
R
Displays the state of the intelli-
gent input terminals
1008h
04101
bit0 = [11]
bit 4 =[15]
terminals
1 bit
D007
H Scaled output frequency
monitor
R
Displays the output frequency
scaled by the constant in B0086.
Decimal point indicates range:
XX.XX 0.00 to 99.99
XXX.X 100.0 to 999.9
XXXX. 1000 to 9999
XXXX 10000 to 99990
1009h
04105
0 to 39960
0.01
D007
L
R
100Ah
04106
D008
H Actual frequency monitor
R
Displays the actual shaft speed of
the motor, converted to
frequency
100Bh
04107
-40000 to
+40000
0.01 Hz
D008
L
R
100Ch
04108
D009
— Torque command monitor
R
Displays the level of the torque
command when the inverter is set
to torque control mode
100Dh
04109
-200 to 200
1 %
D010
— Torque bias monitor
R
Displays the level of the torque
bias, if enabled, when the
inverter is in vector control mode
with feedback
100Eh
04110
-200 to 200
1 %
—
— (Reserved)
R
—
100Fh
04111
—
—
D012
— Torque monitor
R
Estimated output torque value,
range is -300.0 to +300.0%
1010h
04112
-200 to 200
1 %
D013
— Output voltage monitor
R
Voltage of output to motor,
range is 0.0 to 600.0V
1012h
04113
0 to 6000
0.1 V
D014
— Power monitor
R
Input power to inverter,
range is 0.0 to 999.9
1013h
04114
0 to 9999
0.1 kW
D015
H Cumulative power monitor
R
Displays cumulative input power
to inverter; B079 selects the
multiplier for units. Range is 0.0
to 999.9, 1000 to 9999, or 100 to
999
1014h
04115
0 to 9999999
0.1
D015
L
R
1014h
04116
Holding Registers, “D” Group Monitor Functions
Func. Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.