ModBus Data Listing
Append
ix
B
B–50
—
(Reserved)
—
—
3271h
to
330Bh
12913
to
13067
—
—
A094
— Select method to switch to
Acc2/Dec2 profile
R/W
00..[2CH] terminal input
01..transition frequency
02..when motor direction
reverses
1278h
04728
0, 1, 2
—
A294
— Select method to switch to
Acc2/Dec2, 2nd motor
R/W
00..[2CH] terminal input
01..transition frequency
02..when motor direction
reverses
2273h
08819
0, 1, 2
—
A095
H Acc1 to Acc2 frequency
transition point
R/W
Output frequency at which
Accel1 switches to Accel2
1279h
04729
0 to 40000
0.01 Hz
A095
L
R/W
127Ah
04730
A295
H Acc1 to Acc2 frequency
transition point, 2nd motor
R/W
Output frequency at which
Accel1 switches to Accel2
2274h
08820
0 to 40000
0.01 Hz
A295
L
R/W
2275h
08821
A096
H Dec1 to Dec2 frequency
transition point
R/W
Output frequency at which
Decel1 switches to Decel2
127Bh
04731
0 to 40000
0.01 Hz
A096
L
R/W
127Ch
04732
A296
H Dec1 to Dec2 frequency
transition point, 2nd motor
R/W
Output frequency at which
Decel1 switches to Decel2
2276h
08822
0 to 40000
0.01 Hz
A296
L
R/W
2277h
08823
—
(Reserved)
—
—
2278h
to
230Bh
08824
to
08971
—
—
A097
— Acceleration curve
selection
R/W
00..Linear
01..S-curve
02..U-shape
03..Reverse U-shape
04..EL-S curve
127Dh
04733
0 to 4
—
A098
— Deceleration curve setting
R/W
00..Linear
01..S-curve
02..U-shape
03..Reverse U-shape
04..EL-S curve
127Eh
04734
0 to 4
—
—
(Reserved)
—
—
127Fh
04735
—
—
—
(Reserved)
—
—
1280h
04736
—
—
A101
H [OI]–[L] input active range
start frequency
R/W
Output frequency corre-
sponding to the current input
range starting point
1281h
04637
0 to 40000
0.01 Hz
A101
L
R/W
1282h
04738
A102
H [OI]–[L] input active range
end frequency
R/W
Output frequency corre-
sponding to the current input
range ending point
1283h
04739
0 to 40000
0.01 Hz
A102
L
R/W
1284h
04740
A103
— [OI]–[L] input active range
start current
R/W
Starting point for the current
input range
1285h
04741
0 to A104
value
1 %
A104
— [OI]–[L] input active range
end current
R/W
Ending point for the current
input range
1286h
04742
A103
value to
100
1 %
A105
— [OI]–[L] input start
frequency enable
R/W
00..Use A101 start value
01..Use 0Hz
1287h
04743
0, 1
—
Holding Registers, “A” Group Standard Functions
Func. Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.