Inverter Specifications
Geting Star
ted
1–12
Signal Ratings
Detailed ratings are in
“Specifications of Control and Logic Connections” on page 4–9
.
DCL Filter
Specifications
Direct reactor filters (DCL) are available for the Hitachi high-capacity SJ700
2
inverters, models
-1850HFU2 to -4000HFU2. The DCL specifications are in the following table.
Carrier
Frequency
Derating
The maximum carrier frequency F
c
that provides full inverter rated output depends on the
particular inverter model. However, you may operate an inverter at the maximum settable F
c
with an output derating. Refer to the table below for the carrier frequency values and output
deratings.
Signal / Contact
Ratings
Built-in power for inputs
24VDC supply, 100 mA maximum
Intelligent (programmable) logic inputs
27VDC maximum, 4.7k
Ω
input impedance
Intelligent (programmable) logic outputs
Open collector type, 50mA max. ON state current, 27 VDC maximum OFF state voltage
Thermistor input
Minimum thermistor power 100mW
PWM output
0 to 10VDC, 1.2 mA max., 50% duty cycle
Voltage analog output
0 to 10VDC, 2 mA max.
Current analog output
4-20 mA, nominal load impedance 250
Ω
Analog input, current
4 to 19.6 mA range, 20 mA nominal
Analog input, voltage unipolar
0 to 9.6 VDC range, 10VDC nominal, 12VDC max., input impedance 10 k
Ω
Analog input, voltage bipolar
–9.6 to 9.6 VDC range, ±10VDC nominal, ±12VDC max., input impedance 10 k
Ω
+10V analog reference
10VDC nominal, 10 mA maximum
Alarm relay, normally closed contacts
Maximum loads: 250VAC, 2A; 30VDC, 8A resistive load
250VAC, 0.2A; 30VDC, 0.6A inductive load
Minimum loads: 100 VAC, 10mA; 5VDC, 100mA
Alarm relay, normally open contacts
250VAC, 1A; 30VDC 1A max. resistive load /
250VAC, 0.2A; 30VDC, 0.2A max. inductive load
Min. loads: 100 VAC, 10mA; 5VDC, 100mA
Item
DCL Specifications
DCL models, DCL-H-xxx
185
315
400
Rated current (A)
515.0
680
1042
Insulation class
Type H
Weight kg / lb.
65
75
90
200V Class Inverters
Capacity
(kW)
Maximum
F
c
(kHz)
Derating at
Fc = 15 kHz
Capacity
(kW)
Maximum
F
c
(kHz)
Derating at
Fc = 15 kHz
0.4
15
100%
15
12
95% (60.8A or less)
0.75
15
100%
18.5
10
90% (68.4A or less)
1.5
15
100%
22
7
70% (66.5A or less)
2.2
15
100%
30
5
80% (96.8A or less)
3.7 / 4.0
15
100%
37
10
75% (108.7A or less)
5.5
15
100%
45
5
70% (127.4A or less)
7.5
15
100%
55
5
70% (154.0A or less)
11
12
90% (41.4A or less)
—
—
—