SJ700
2
Inverter
xiii
Terminal Tighten-
ing Torque and
Wire Size
The wire size range and tightening torque for field wiring terminals are presented in the table
below.
Input
Voltage
Motor
Output
200V
Inverter Model
Wire Size Range (AWG)
Torque
HP
kW
ft-lbs
(N-m)
200V
0.5
0.4
SJ700–004LFU2
14 (stranded only)
1.3
1.8
1
0.75
SJ700–007LFU2
14 (stranded only)
1.3
1.8
2
1.5
SJ700–015LFU2
14 (stranded only)
1.3
1.8
3
2.2
SJ700–022LFU2
14 (stranded only)
1.3
1.8
5
3.7
SJ700–037LFU2
10 (stranded only)
1.3
1.8
7.5
5.5
SJ700-055LFU2
8
3.0
4.0
10
7.5
SJ700-075LFU2
6
3.0
4.0
15
11
SJ700-110LFU2
6–4
3.0
4.0
20
15
SJ700-150LFU2
2
3.6
4.9
25
18.5
SJ700-185LFU2
1
3.6
4.9
30
22
SJ700-220LFU2
1 or 1/0
6.5
8.8
40
30
SJ700-300LFU2
2/0 or 1/0 || 1/0
6.5
8.8
50
37
SJ700-370LFU2
4/0 (prepared wire only) or
1/0 || 1/0
14.8
20.0
60
45
SJ700-450LFU2
4/0 (prepared wire only) or
1/0 || 1/0
14.8
20.0
75
55
SJ700-550LFU2
350 kcmil (prepared wire
only) or 2/0 || 2/0 (prepared
wire only
14.5
19.6
Input
Voltage
Motor
Output
400V
Inverter Model
Power Terminals
Wire Size Range (AWG)
Torque
HP
kW
ft-lbs
(N-m)
400V
0.5
0.75
SJ700–007HFU2/E
(All)
14 (stranded only)
1.3
1.8
1
1.5
SJ700–015HFU2/E
(All)
14 (stranded only)
1.3
1.8
2
2.2
SJ700–022HFU2/E
(All)
14 (stranded only)
1.3
1.8
3
4.0
SJ700–040HFU2/E
(All)
14 (stranded only)
1.3
1.8
7.5
5.5
SJ700-055HFU2/E
(All)
12
3.0
4.0
10
7.5
SJ700-075HFU2/E
(All)
10
3.0
4.0
15
11
SJ700-110HFU2/E
(All)
8
3.0
4.0
20
15
SJ700-150HFU2/E
(All)
6
3.6
4.9
25
18.5
SJ700-185HFU2/E
(All)
6
3.6
4.9
30
22
SJ700-220HFU2/E
(All)
6 or 4
6.5
8.8
40
30
SJ700-300HFU2/E
(All)
3
6.5
8.8
50
37
SJ700-370HFU2/E
(All)
1
14.8
20.0
60
45
SJ700-450HFU2/E
(All)
1
14.8
20.0
75
55
SJ700-550HFU2/E
(All)
2/0
14.5
19.6