SJ700
2
Inverter
Appendix B
B–43
Holding Registers, “A” Group Standard Functions
Func. Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.
A001
— Frequency source setting
R/W
00 . Keypad potentiometer
01 . Control terminal
02 . Function F001 setting
03 . RS485 serial command
04 . Expansion board #1
05 . Expansion board #2
06 . Pulse train input
07 . Easy sequence
10 . Caltulate function input
1201h
04609
00 to 07,
10
—
A002
— Run command source
setting
R/W
01 . Input [FW] or [RV]
02 . Run key on keypad
03 . RS485 serial command
04 . Start/stop, Exp. card #1
05 . Start/stop. exp. card #2
1202h
04610
01 to 05
—
A003
— Base frequency setting
R/W
30. to max. frequency (Hz)
1203h
04611
30 to
A004 val.
1 Hz
A203
— Base frequency setting,
2nd motor
R/W
30. to max. frequency (Hz)
2203h
08707
30 to
A004 val.
1 Hz
A303
— Base frequency setting, 3rd
motor
R/W
30. to max. frequency (Hz)
3203h
12803
30 to
A004 val.
1 Hz
A004
— Maximum frequency
setting
R/W
30. to 400. (Hz)
1204h
04612
30 to 400
1 Hz
A204
— Maximum frequency
setting, 2nd motor
R/W
30. to 400. (Hz)
2204h
08708
30 to 400
1 Hz
—
(Reserved)
—
—
2205h
to
2215h
08709
to
08725
—
—
A304
— Maximum frequency
setting, 3rd motor
R/W
30. to 400. (Hz)
3204h
12804
30 to 400
1 Hz
—
(Reserved)
—
—
3205h
to
3215h
12805
to
12821
—
—
A005
— [AT] selection
R/W
00 . Select between [O] and
[OI] at [AT]
01 . Select between [O] and
[O2] at [AT]
02 . Select between [O] and
keypad pot.
03 . Select between [OI] and
keypad pot.
04 . Select between [O2] and
keypad pot.
1205h
04613
00 to 04
—
A006
— [O2] selection
R/W
00 . No summing, [O2] and
[OI]
01 . Sum of [O2] and [OI],
neg. sum (reverse speed
reference) inhibited
02 . Sum of [O2] and [OI],
neg. sum (reverse speed
reference) allowed
03 . Disable [O2] input
1206h
046
00 to 03
—