B084, B085: Initialization codes –
These functions allow you to restore the factory default
settings. Please refer to
“Restoring Factory Default Settings” on page 6–16
.
B086: Frequency display scaling –
You can convert the output frequency monitor on D001 to
a scaled number (engineering units) monitored at function D007. For example, the motor may
run a conveyor that is monitored in feet per minute. Use this formula:
B091/B088: Stop Mode / Restart Mode Configuration –
You can configure how the inverter
performs a standard stop (each time Run FWD and REV signals turn OFF). Setting B091 deter-
mines whether the inverter will control the deceleration, or whether it will perform a free-run
stop (coast to a stop). When using the free-run stop selection, it is imperative to also configure
how you want the inverter to resume control of motor speed. Setting B088 determines whether
the inverter will ensure the motor always resumes at 0 Hz, or whether the motor resumes from
its current coasting speed (also called
frequency matching
). The Run command may turn OFF
briefly, allowing the motor to coast to a slower speed from which normal operation can resume.
In most applications a controlled deceleration is desirable, corresponding to B091=00.
However, applications such as HVAC fan control will often use a free-run stop (B091=01). This
practice decreases dynamic stress on system components, prolonging system life. In this case,
you will typically set B088=01 in order to resume from the current speed after a free-run stop
(see diagram below, right). Note that using the default setting, B088=00, can cause trip events
when the inverter attempts to force the load quickly to zero speed.
Scaled output frequency (D007)
Output frequency (D001)
Factor (B086)
×
=
Func.
Code
Name/
Description
Keypad
Range and Settings
Defaults
Run
Mode
Edit
Lo Hi
SRW
OPE
FEF2
FE2
(EU)
FUF2
FU2
(USA)
FF2
F2
(Jpn)
B078
Clear cumulative input power
data
CNT
00
No change
00
00
00
✔ ✔
Set = 01, press STR key to clear
CLR
0 1
Clear the data
B079
Cumulative input power display gain setting
1. to 1000.
1.
1.
1.
✔ ✔
B082
Start frequency adjustment
0.10 to 9.99 (Hz)
0.50
0.50
0.50
✘ ✔
Sets the starting frequency for the inverter output
B083
Carrier frequency setting
Most models, 0.5 to 15.0 (kHz);
-1850 and -3150 are 0.5 to 10 (kHz);
-4000 is 0.5 to 3 (kHz)
3.0
2.1
1.9
3.0
2.1
1.9
3.0
2.1
1.9
✘ ✔
Sets the PWM carrier (internal switching freq.);
all models are subject to derating
✘ ✔
B084
Initialization mode (parameters
or trip history)
TRP
00
Trip history clear
00
00
00
✘ ✘
DATA
0 1
Parameter initialization
TRP/
DATA
02
Trip history clear and parameter
initialization
B085
Country code for initialization
JPN
00
Japan version
01
02
00
✘ ✘
Select default parameter values
for country on initialization
EUR
0 1
Europe version
USA
02
USA version
B086
Frequency scaling conversion factor
0.1 to 99.9
1.0
1.0
1.0
✔ ✔
Specify a constant to scale D007 to display in
engineering units
B087
STOP key enable
ON
00
Enable
00
00
00
✘ ✔
Select whether the STOP key on
the keypad is enabled (req.
A002=01, 03, 04, or 05)
OFF
0 1
Disable
S-OFF
02
Disable only the STOP function