How to Order
—
Factory Ranged and Configured
Options
Model
Power
Input
Outputs
Alarm
Code
Description
APD 41393
85-265 VAC, 60-300 VDC
Specify
T/C type,
temperature
range in
°F or °C
Ch. 1
specify
VDC or mADC
range
Custom
Push-to-Test
___% span
Ch. 2
specify
VDC or mADC
range
Custom
Push-to-Test
___% span
none
-
B
N
RA
HP
HT
U
Upscale burnout (standard)
Downscale burnout
No burnout, last valid value
Reverse-acting alarm
Latching relay, power-off reset
Latching relay, push button reset
Conformal coating for moisture
resistance
APD 41393 D
9-30 VDC, 10-32 VAC
APD 41393 H
85-265 VAC, 60-300 VDC
HI alarm
(failsafe std.)
APD 41393 DH
9-30 VDC, 10-32 VAC
APD 41393 L
85-265 VAC, 60-300 VDC
LO alarm
(failsafe std.)
APD 41393 DL
9-30 VDC, 10-32 VAC
Thermocouple Input to Dual DC Output Splitter/Converter, Factory Ranged
APD 41393
1 Input:
Any Thermocouple
2 Outputs:
Two Independent Process Voltage or mA Signals, Alarm Relay Options
O
Split or Convert a T/C Into 2 Independent DC Outputs
O
Add Additional Isolated Output to Existing T/C
O
Zero and Span Output Calibration
O
Input LoopTracker
®
LED
O
Sink/Source for DC Outputs
Q
Split/Isolate T/Cs for PLC Input, Control or Validation
Q
Interface Thermocouples with Panel Meters, PLCs,
Recorders, Data Acq., DCS, & SCADA Systems
Applications
Thermocouple Input, Factory Set
T/C types:
J, K, T, E, M, N, P, R, S, B, C, D, G
Temp. range: Full ANSI range, or specify °F or °C range
Linearity:
±0.1°C and 0.001°C resolution
Linearization: Polynomials, 1°C segments for types M and P
T/C CJC:
Automatic
T/C current: Less than 10 µA, including burnout sense
T/C burnout: Upscale (standard),
B
: downscale,
N
: none
Custom:
Provide T/C millivolt data, °F or °C range
Status LEDs
LoopTracker:
Variable brightness green for input level
Yellow LED:
Output Push-to-Test status, error status
Red/green LED: Alarm state (with alarm option only)
DC Output, Channel 1, Factory Set
Linearized to temperature
Voltage:
0-1 V to 0-10 V (10 mA max.), ±1 V to ±10 V
Current:
0-1 mA to 0-20 mA
20 V compliance, 1000
Ω
at 20 mA
Sinking or sourcing output
Loop power: 20 VDC nom., regulated, 25 mADC
<10 mV
RMS
max. ripple
DC Output, Channel 2, Factory Set
Linearized to temperature
Voltage:
0-1 V to 0-10 V (10 mA max.), ±1 V to ±10 V
Current:
0-1 mA to 0-20 mA
20 V compliance, 1000
Ω
at 20 mA
Sinking or sourcing output
Loop power: 20 VDC nom., regulated, 25 mADC
<10 mV
RMS
max. ripple
Output Calibration
Zero and span potentiometers for each output, ±15% range
Output Push-to-Test (Output 1 & Output 2)
Front push buttons and terminals enable/disable test level out-
puts. Each set to 75% of output span. Specify custom setting.
Output Resolution
16 bit
Output Ripple and Noise
Less than ±0.2% of span
Optional Alarm Relay
Single setpoint dual DPST contact sets, factory configured
1 Form A (NO) and 1 Form B (NC) contact sets (4 terminals)
May be field wired for Form C operation
8 A max @ 240 VAC
resistive load
Use external contact
protection (RC snub-
ber) for inductive loads
Red/Green bi-color
LED indicates alarm
status
One set point, 12
turn potentiometer,
0-100% of span
One reset point, 12 turn potentiometer, 0-100% of span
Default: HI alarm, non-latching, normal acting (failsafe)
Relay Test button toggles relay to opposite state or resets
relay with HT option
Ambient Temperature Range and Stability
–10°C to +60°C operating ambient
Better than ±0.02% of span per °C stability
Response Time
500 milliseconds minimum
Isolation
© 02-20
api-usa.com
1220 American Way Libertyville, IL 60048
Phone:
800-942-0315
Fax: 800-949-7502
A
A
BSOLUTE
BSOLUTE
P
P
ROCESS
ROCESS
I
I
NSTRUMENTS
NSTRUMENTS
Removable Plugs
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
25 26 27 28
29 30 31 32
17 18 19 20
21 22 23 24
See Wiring
Diagrams on
Next Page
Quick Link:
api-usa.com/tc
Full 4-way galvanic: input, output 1, output 2,
power, 1200 V
RMS
min.
600 VACp or 600 VDC common mode protection
75 dB minimum common mode rejection
Simultaneous 50 Hz and 60 Hz rejection
Housing and Connectors
IP 40, requires vertical installation on a 35 mm DIN
rail inside a panel or enclosure. Allow room for
air flow. For use in Pollution Degree 2 Environment.
Eight 4-terminal removable connectors,
14 AWG max. wire size
Power
85-265 VAC, 50/60 Hz or 60-300 VDC, 3 W maximum
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 3 W maximum
Dimensions
1.78" W x 4.62" H x 4.81" D
(45 mm W x 117 mm H x 122 mm D)
Switching Current (A)
Switching Voltage (V)
0
3 5 10
30 50 100 300 500
8
5
3
1
0.5
0.3
0.1
AC inductive load
(cos
f
= 0.4)
AC resistive
load
DC inductive load
(L/R = 7 ms)
DC resistive
load
Free Factory
I/O Setup!
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
Made in USA
Applications Link
api-usa.com/apps
Pb
Lead
Free
Sink or Source
Output for
mADC Channels
Output Test for
DC Channels
Universal Power
Optional Alarm
Relay
Input
LoopTracker
LED
Zero and
Span for
Each Output
Status LED
Description
The APD 41393 accepts a thermocouple temperature input and
provides two independent DC process outputs. This makes it
useful to split, isolate, and transmit a thermocouple signal for
measurement, data recording, or validation.
The thermocouple input type and temperature range are fac-
tory set. The two DC output types and ranges are factory set.
The DC outputs can be different and both correspond to the
input temperature range specified. Use appropriate thermo-
couple extension wire for the input as needed.
The input is sampled, CJC compensated, digitally converted to
a linearized temperature signal, and then passed to the output
stages where it is converted to the two DC outputs.
Output Sink/Source Versatility
The APD 41393 includes a 20 VDC loop excitation supply for
any channel ordered with a mA output. A mA output can be
selectively wired for sinking or sourcing allowing use with a
powered or unpowered milliamp device.
Full 4-way galvanic isolation (input, output 1, output 2, power)
make this module useful for ground loop elimination, common
mode signal rejection, and noise pickup reduction.
LoopTrackers
An API exclusive feature includes a green LoopTracker LED
that varies in intensity with changes in the input signal and
red LoopTracker LEDs that vary in intensity with changes in
the DC output signals. It provides a quick visual picture of your
process at all times and can greatly aid in saving time during
initial startup and troubleshooting.
Output Push-to-Test
An API exclusive feature includes output test switches for each
DC output to provide a fixed output (independent of the input)
when pressed. The output test greatly aids in saving time dur-
ing initial startup and/or troubleshooting.
The output test level is factory set to approximately 75% of
span but a custom test level may be ordered.