Figure 51:
Two differential protection solutions for delta-wye connected power
transformer
For this particular power transformer the 115 kV side phase-to-ground no-load voltages
lead by 30° the 24.9 kV side phase-to-ground no-load voltages. Thus when external
phase angle shift compensation is done by connecting main 24.9 kV CTs in delta, as
shown in the right-hand side in figure
, it must be ensured that the 24.9 kV currents
are rotated by 30° in anti-clockwise direction. Thus, the DAB CT delta connection (see
figure
) must be used for 24.9 kV CTs in order to put 115 kV & 24.9 kV currents in
phase.
To ensure proper application of the IED for this power transformer it is necessary to do
the following:
1. Check that HV & LV CTs are connected to 5 A CT inputs in the IED.
2. For second solution make sure that LV delta connected CTs are DAB connected.
3. For wye connected CTs make sure how they are 'star'red (that is, grounded) to/from
protected transformer.
4. Enter the following settings for all three CT input channels used for the HV side
CTs, see table
1MRK 504 163-UUS A
Section 7
Differential protection
Transformer protection RET670 2.2 ANSI
151
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...