![ABB RELION RET670 Applications Manual Download Page 115](http://html.mh-extra.com/html/abb/relion-ret670/relion-ret670_applications-manual_4714115.webp)
Section 6
Wide area measurement system
6.1
C37.118 Phasor Measurement Data Streaming
Protocol Configuration PMUCONF
GUID-747C6AD7-E6A1-466E-92D1-68865681F92F v1
6.1.1
Identification
GUID-1E140EA0-D198-443A-B445-47CEFD2E6134 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Configuration parameters for IEEE
1344 and C37.118 protocol
PMUCONF
-
-
6.1.2
Application
GUID-33694C62-A109-4D8F-9063-CEFA5D0E78BC v4
The IED supports the following IEEE synchrophasor standards:
•
IEEE 1344-1995 (Both measurements and data communication)
•
IEEE Std C37.118-2005 (Both measurements and data communication)
•
IEEE Std C37.118.1–2011 and C37.118.1a-2014 (Measurements)
•
IEEE Std C37.118.2-2011 (Data communication)
PMUCONF contains the PMU configuration parameters for both IEEE C37.118 and
IEEE 1344 protocols. This means all the required settings and parameters in order to
establish and define a number of TCP and/or UDP connections with one or more PDC
clients (synchrophasor client). This includes port numbers, TCP/UDP IP addresses, and
specific settings for IEEE C37.118 as well as IEEE 1344 protocols.
6.1.3
Operation principle
GUID-2608FBC4-9036-476A-942B-13452019BC11 v2
demonstrates the communication configuration diagram. As can be seen,
the IED can support communication with maximum 8 TCP clients and 6 UDP client
groups, simultaneously. Every client can communicate with only one instance of the
two available PMUREPORT function block instances at a time. It means that one client
cannot communicate with both PMUREPORT:1 and PMUREPORT:2 at the same time.
However, multiple clients can communicate with the same instance of PMUREPORT
function block at the same time. For TCP clients, each client can decide to
communicate with an existing instance of PMUREPORT by knowing the
1MRK 504 163-UUS A
Section 6
Wide area measurement system
Transformer protection RET670 2.2 ANSI
109
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...