must operate very quickly for faults very close to the generation (and relay) point, for
which very high fault currents are characteristic.
The instantaneous phase overcurrent protection PHPIOC (50) can operate in 10 ms for
faults characterized by very high currents.
9.1.3
Setting guidelines
IP14979-1 v1
M12915-4 v9
The parameters for instantaneous phase overcurrent protection PHPIOC (50) are set via
the local HMI or PCM600.
This protection function must operate only in a selective way. So check all system and
transient conditions that could cause its unwanted operation.
Only detailed network studies can determine the operating conditions under which the
highest possible fault current is expected on the line. In most cases, this current appears
during three-phase fault conditions. But also examine single-phase-to-ground and two-
phase-to-ground conditions.
Also study transients that could cause a high increase of the line current for short times.
A typical example is a transmission line with a power transformer at the remote end,
which can cause high inrush current when connected to the network and can thus also
cause the operation of the built-in, instantaneous, overcurrent protection.
Common base IED values for primary current (
IBase
), primary voltage (
UBase
) and
primary power (
SBase
) are set in the global base values for settings function
GBASVAL.
GlobalBaseSel
: This is used to select GBASVAL function for reference of base values.
Operation
: Set the protection to
On
/
Off
.
OpModeSel
: This parameter can be set to
2 out of 3
or
1 out of 3
. The setting controls
the minimum number of phase currents that must be larger than the set operate current
Pickup
for operation. Normally this parameter is set to
1 out of 3
and will thus detect all
fault types. If the protection is to be used mainly for multi phase faults,
2 out of 3
should be chosen.
Pickup
: Set operate current in % of
IB
.
IP>>Max
and
IP>>Min
should only be changed if remote setting of operation current
level,
IP>>
, is used. The limits are used for decreasing the used range of the
IP>>
setting. If
IP>>
is set outside
IP>>Max
and
IP>>Min
, the closest of the limits to
IP>>
is used by the function. If
IP>>Max
is smaller than
IP>>Min
, the limits are
swapped.
Section 9
1MRK 504 163-UUS A
Current protection
514
Transformer protection RET670 2.2 ANSI
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...