When V
B
falls below setting
Vblock
, or alternatively, falls below setting
Vmin
but still
above
Vblock
, or rises above
Vmax
, actions will be taken in accordance with settings
for blocking conditions (refer to table
If the busbar voltage rises above
Vmax
, TR1ATCC (90) can initiate one or more fast
step down commands (VLOWER commands) in order to bring the voltage back into
the security range (settings
Vmin
, and
Vmax
). The fast step down function operation
can be set in one of the following three ways: off /auto/auto and manual, according to
the setting
FSDMode
. The VLOWER command, in fast step down mode, is issued with
the settable time delay
tFSD
.
The measured RMS magnitude of the busbar voltage V
B
is shown on the local HMI as
value BUSVOLT under
Main menu/Test/Function status/Control/
TransformerVoltageControl(ATCC,90)/TR1ATCC:x/TR8ATCC:x
.
Time characteristic
SEMOD159053-82 v5
The time characteristic defines the time that elapses between the moment when
measured voltage exceeds the deadband interval until the appropriate VRAISE or
VLOWER command is initiated.
The purpose of the time delay is to prevent unnecessary load tap changer operations
caused by temporary voltage fluctuations and to coordinate load tap changer operations
in radial networks in order to limit the number of load tap changer operations. This can
be done by setting a longer time delay closer to the consumer and shorter time delays
higher up in the system.
The first time delay,
t1
, is used as a time delay (usually long delay) for the first
command in one direction. It can have a definite or inverse time characteristic,
according to the setting
t1Use
(Constant/Inverse). For inverse time characteristics
larger voltage deviations from the
VSet
value will result in shorter time delays, limited
by the shortest time delay equal to the
tMin
setting. This setting should be coordinated
with the tap changer mechanism operation time.
Constant (definite) time delay is independent of the voltage deviation.
The inverse time characteristic for the first time delay follows the formulas:
DA
VB VSet
=
-
ANSIEQUATION2294 V1 EN-US
(Equation 504)
DA
D
V
=
D
EQUATION1846-ANSI V1 EN-US
(Equation 505)
Section 15
1MRK 504 163-UUS A
Control
760
Transformer protection RET670 2.2 ANSI
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...