Parameters to be set are MODE, common for the whole block, and CMDOUTy which
includes the user defined name for each output signal. The MODE input sets the
outputs to be one of the types Disabled, Steady, or Pulse.
•
Disabled, sets all outputs to 0, independent of the values sent from the station
level, that is, the operator station or remote-control gateway.
•
Steady, sets the outputs to a steady signal 0 or 1, depending on the values sent
from the station level.
•
Pulse, gives a pulse with 100 ms duration, if a value sent from the station level is
changed from 0 to 1. That means the configured logic connected to the command
function block may not have a cycle time longer than the cycle time for the
command function block.
Section 15
1MRK 504 163-UUS A
Control
810
Transformer protection RET670 2.2 ANSI
Application manual