Disabled
•
SNTP -Server
Set the course time synchronizing source (
CoarseSyncSrc
) to
Disabled
when GPS time synchronization of line differential function is used. Set
the fine time synchronization source (
FineSyncSource
) to
GPS
. The
GPS will thus provide the complete time synchronization. GPS alone
shall synchronize the analogue values in such systems.
IEEE 1588 (PTP)
GUID-424227EC-74A1-4628-8948-C1876840ABFE v2
Precision Time Protocol (PTP) is enabled/disabled using the Ethernet configuration
tool /ECT) in PCM600.
PTP
can be set to
On
,
Off
or
Slave only
. When set to
Slave only
the IED is connected to
the PTP-group and will synchronize to the grandmaster but cannot function as the
grandmaster.
A PTP-group is set up by connecting the IEDs to a network and enabling PTP. To set
one IED as the grandmaster change Priority2 to 127 instead of the default 128.
IEC16000089-1-en.vsdx
IEC16000089 V1 EN-US
Figure 432:
Enabling PTP in ECT
The
PTP VLAN
tag must have the same value in station clock and in the IED. The
default value is set to 0.
The
PTP VLAN
tag does not need to be the same on all access points in one IED. It is
possible to mix as long as they are the same for all devices on each subnet.
1MRK 504 163-UUS A
Section 24
Basic IED functions
Transformer protection RET670 2.2 ANSI
981
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...