IED
ZB
Line impedance = ZC
ZA = forward source impedance
IEC07000014_2_en.vsd
IEC07000014 V2 EN-US
Figure 237:
Line application of pole slip protection
If the apparent impedance crosses the impedance line ZB – ZA this is the detection
criterion of out of step conditions, see figure
.
Section 8
1MRK 504 163-UUS A
Impedance protection
472
Transformer protection RET670 2.2 ANSI
Application manual