t2MPh
: Time delay of the back-up trip at multi-phase initiate. The critical fault
clearance time is often shorter in case of multi-phase faults, compared to single phase-
to-ground faults. Therefore there is a possibility to reduce the back-up trip delay for
multi-phase faults. Typical setting is 90 – 150 ms.
t3
: Additional time delay to
t2
for a second back-up trip TRBU2. In some applications
there might be a requirement to have separated back-up trip functions, tripping
different back-up circuit breakers.
tCBAlarm
: Time delay for alarm in case of indication of faulty circuit breaker. There is
a binary input 52FAIL from the circuit breaker. This signal is activated when internal
supervision in the circuit breaker detect that the circuit breaker is unable to clear fault.
This could be the case when gas pressure is low in a SF6 circuit breaker. After the set
time an alarm is given, so that actions can be done to repair the circuit breaker. The
time delay for back-up trip is bypassed when the 52FAIL is active. Typical setting is
2.0 seconds.
tPulse
: Trip pulse duration. This setting must be larger than the critical impulse time of
circuit breakers to be tripped from the breaker failure protection. Typical setting is 200
ms.
9.10
Stub protection STBPTOC (50STB)
IP14515-1 v3
9.10.1
Identification
M17108-1 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Stub protection
STBPTOC
3I>STUB
SYMBOL-T V1 EN-US
50STB
9.10.2
Application
M12904-3 v5
In a breaker-and-a-half switchyard the line protection and the busbar protection
normally have overlap when a connected object is in service. When an object is taken
out of service it is normally required to keep the diagonal of the breaker-and-a-half
switchyard in operation. This is done by opening the disconnector to the protected
object. This will, however, disable the normal object protection (for example the
distance protection) of the energized part between the circuit breakers and the open
disconnector.
1MRK 504 163-UUS A
Section 9
Current protection
Transformer protection RET670 2.2 ANSI
575
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...