ANSI11000232-3-en.vsd
AND
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
Start signal to
remote side
Start signal from
remote side
Release of line
differential
protection trip
LDLPSCH (87L)
CTFAIL
OUTSERV
BLOCK
TRIP
TRL1
TRL2
TRL3
TRLOCAL
TRLOCL1
TRLOCL2
TRLOCL3
TRREMOTE
DIFLBLKD
LDRGFC (11REL)
I3P*
U3P*
BLOCK
BLKCV
BLKUC
BLK3I0
BLKUV
REMSTUP
START
STCVL1L2
STCVL2L3
STCVL3L1
STUC
ST3I0
STUV
ANSI11000232 V3 EN-US
Figure 67:
Local release criterion configuration for line differential protection
7.4.3
Setting guidelines
GUID-3C315FA5-8262-416D-A8ED-927FE0BFAB8F v3
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
VBase
and
SBase
as applicable.
tStUpReset
: Reset delay of the startup signal. The default value is recommended.
Settings for phase-phase current variation subfunction are described below.
Enable CV
:
Enabled
/
Disabled
, is set
Enabled
in most applications
Pick Up ICV
: Level of fixed threshold given in % of
IBase
. This setting should be
based on fault calculations to find the current increase in case of a fault at the point on
the protected line giving the smallest fault current to the protection. The phase current
shall be calculated for different types of faults (single phase-to-ground, phase-to-phase
to ground, phase-to-phase and three phase short circuits) at different switching states in
the network. In case of switching of large objects (shunt capacitor banks, transformers,
and so on) large change in current can occur. The
Pick Up ICV
setting should ensure
that all multi-phase faults are detected.
Time Delay CV
: Time delay of zero sequence overcurrent criterion. Default value 0.002
s is recommended
Settings for zero sequence current criterion subfunction are described below.
Enable 3I0
:
Enabled
/
Disabled
, is set
Enabled
for detection of phase-to-ground faults
with high sensitivity
Section 7
1MRK 504 163-UUS A
Differential protection
186
Transformer protection RET670 2.2 ANSI
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...