en99000044_ansi.vsd
Strong
source
LINE 1
LINE 2
A:1
A:2
B:1
B:2
A
B
Weak
source
CLOSED
CLOSED
OPEN
CLOSED
FAULT
ANSI99000044 V1 EN-US
Figure 388:
Current distribution for a fault close to B side when breaker B1 has
opened
To handle this the send signal CS or CSLn from B2 is held back until the reverse zone
IRVLn has reset and the
tDelayRev
time has been elapsed. To achieve this the reverse
zone on the distance protection shall be connected to input IRV and the output IRVL
shall be connected to input BLKCS on the communication function block ZCPSCH.
The function can be blocked by activating the input IRVBLK or the general BLOCK
input.
16.3.2.2
Weak-end infeed logic
M13895-16 v7
Permissive communication schemes can basically operate only when the protection in
the remote IED can detect the fault. The detection requires a sufficient minimum fault
current, normally >20% of . The fault current can be too low due to an open breaker or
low short-circuit power of the source. To overcome these conditions, weak-end infeed
(WEI) echo logic is used. The fault current can also be initially too low due to the fault
current distribution. Here, the fault current increases when the breaker opens at the
strong terminal, and a sequential tripping is achieved. This requires a detection of the
fault by an independent tripping zone 1. To avoid sequential tripping as described, and
when zone 1 is not available, weak-end infeed tripping logic is used. The weak end
infeed function only works together with permissive overreach communication
schemes as the carrier send signal must cover the complete line length.
The WEI function sends back (echoes) the received signal under the condition that no
fault has been detected on the weak-end by different fault detection elements (distance
protection in forward and reverse direction).
Also, the WEI function can be extended to trip the breaker in the weak side. The trip is
achieved when one or more phase voltages are low during an echo function.
In case of single-pole tripping, the phase voltages are used as phase selectors together
with the received signal CRLn.
Together with the blocking teleprotection scheme some limitations apply:
•
Only the trip part of the function can be used together with the blocking scheme. It
is not possible to use the echo function to send the echo signal to the remote line
1MRK 504 163-UUS A
Section 16
Scheme communication
Transformer protection RET670 2.2 ANSI
827
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...