IEC140000127-2-en.vsd
IEC140000127 V2 EN-US
Figure 42:
An example of correct connection of SMAI and PHASORREPORT
blocks in ACT
Figure
shows an example of wrong connection of SMAI and PHASORREPORT
blocks in ACT where the same SMAI block is connected to different
PHASORREPORT blocks with different instance numbers. Such connection will be
only correct if both connected PHASORREPORT blocks have similar settings for
SvcClass and ReportRate. If settings for PMUREPORT instances differ for SvcClass or
ReportRate, then PHASOR1 connection in PHASORREPORT1 instance 2 will not be
compliant with IEEE C37.118 standard. The reason is that the filtering in SMAI/
3PHSUM block is adapted according to the performance class (SvcClass) and
reporting rate of the connected instance of PHASORREPORT function block. In this
example, SMAI1 will adapt its filtering according to PHASORREPORT instance 1
(because of higher priority) and therefore PHASORREPORT instance 2 will receive
data which does not match its performance class and report rate.
1MRK 504 163-UUS A
Section 6
Wide area measurement system
Transformer protection RET670 2.2 ANSI
125
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...