background image

Visit

www.rmspl.com.au

  for the latest product information.

Due to RMS continuous product improvement policy this information is subject to change without notice. 1S25/Issue F/07/03/2011 - 1/9

Features

Four independent arc fault

tripping zones

1 or 2 arc fault sensors per

zone allowing up to 8 arc fault

sensors per 1S25 module

Trip indication LED for each arc

fault monitoring zone

Non volatile memory ensures

last recorded alarm states are

restored on power up

Nine (9) high speed arc fault

tripping duty output contacts

(Set for latching or self reset)

Zone segregated or common

tripping output configuration

Continuous arc sensor

supervision with sensor fail

LED for each zone

Wide range status input to

block arc fault monitoring

Front panel reset button &

status input

Self supervision watchdog with

healthy LED & alarm contact

Built in test sequence

Wide range auxiliary supply

Introduction

Medium  voltage  switchgear  is  a  key

element  in the  power  supply  chain.

Existing  protection  systems  operate

effectively under most circumstances, but

they  are  too  slow  to  handle  arcing  short

circuits.
Arcing  faults  can  occur as  a  result  of

insulation  breakdown  due  to  equipment

age & / or poor maintenance.
The  degree  of  damage  caused  by  arcing

depends principally on the duration of the

arc.  If  an  arc  lasts  only  100ms,  the

switchgear  needs  to  be  checked &  the

insulation  resistance  measured  before

power  can  be  re-established.  With  a

200ms  arc,  the  power  supply  will  be

interrupted;  the  switchgear  must  be

checked;  power  is  re-established  only

after  minor  repairs.  In  the  event  of  a

500ms arc the supply is interrupted, metal

parts  of  the  switchgear  are  destroyed &

poisonous  gases  are  emitted.  A  1s  arc

destroys  most  of  the  switchgear &  may

cause a fire, injury to personnel & damage

to property.

Technical Bulletin

1S25

Arc Fault Monitor – 4 Zones, 8 Sensors

1S25 depicted in a 2M28-S draw out case

with custom alarm text engraving

ARC Fault Protection

      Made in Australia

Arc fault protection is a relatively new technique employed for the fast clearance of arcing

faults  on low  voltage  panels, MCC’s, BUS  bars &  within  metal  clad switchgear &

associated cable boxes. The arc is detected using an optical sensor & the signal input to a

protection device which also monitors the load current on the system. A trip signal can be

achieved in  less  than  10ms  using  arc  detection  only  or within  15ms when  using

overcurrent check. This is considerably faster than a traditional IDMT overcurrent relay &

provides  additional  protection  from the  onset  of  arcing  faults with relatively  low  fault

currents.
Arguably the greatest risk of arc fault damage exists at the CB cable termination & in the

CB chamber itself due to the slow clearance times of the IDMT feeder protection. The CB

cable termination is particularly at risk to ingress of moisture & rodent damage.
The problem of arc faults is most prevalent in older metal clad switchgear which already

has  operational  protection  systems.  The  1S25  Arc  Fault  Monitor  has  therefore  been

designed for the following applications:

EXISTING SWITCHGEAR

Where a requirement exists to retrofit arc fault protection to metal clad switchgear utilizing

the existing overcurrent protection relay;

NEW SWITCHGEAR

Where a requirement exists to install arc fault protection to new switchgear for integration

with the customer preferred overcurrent feeder protection relay;

LOW VOLTAGE PANELS

Arc  fault  protection  may  also  be applied  on  low  voltage  panel  control  boards  &  motor

control centers (MCC’s).

Summary of Contents for 1S25 Series

Page 1: ...oyed poisonous gases are emitted A 1s arc destroys most of the switchgear may cause a fire injury to personnel damage to property Technical Bulletin 1S25 Arc Fault Monitor 4 Zones 8 Sensors 1S25 depicted in a 2M28 S draw out case with custom alarm text engraving ARC Fault Protection Made in Australia Arc fault protection is a relatively new technique employed for the fast clearance of arcing fault...

Page 2: ...n independent output contact associated with the start current setting of the relay That is an output contact that will close when a phase or earth fault current is detected above the threshold which starts the internal relay timers This starter element should be set for instantaneous operation so that it will pick up in the order of 15ms An Arc Fault Monitor relay 1S25 is installed on the switchg...

Page 3: ...ROTECTION Figure 5 depicts how the 1S25 may also be applied for the protection of bus bars The number of sensors in the bus chamber is dictated by the switchgear design and the length of switchboard In most indoor metal clad switchgear the bus bar chamber is a continuous chamber between panels only broken into segregated sections at a bus section breaker as such the strategic placement of one or t...

Page 4: ... switchgear Over current check stage depicted Low Voltage Applications LOW VOLTAGE ARC PROTECTION Figures 6 7 depict how the 1S25 may also be applied for low voltage panels MCC switchgear Figure 6 depicts an arrangement where over current check stage is employed while the protection application depicted in figure 7 is a system based solely on arc detection 1S25 HEALTH Y ZONE 2 ZONE 3 ZONE 4 ZONE 1...

Page 5: ...pping scheme usually results in reduced system security The arc detection method can however combine the 1S25 optical detection technique with a traditional overcurrent method to maximize system security particularly for BUS bar protection schemes Both conditions must coexist for the trip condition to be met as depicted in figure 8 ARC FAULT TRIP INITIATE CB ARC FAULT MONITOR SENSOR OVER CURRENT R...

Page 6: ... panels STATUS INPUT MINIMUM OPERATING CURRENT 10mA P U for 1ms then reducing to1 5mA after 4ms RESET Press the front reset button or pulse the reset status input Technical Data OUTPUT CONTACTS Tripping contacts 8 2 N O per tripping zone Common tripping contact 1 N O Fail alarm 1 C O contact for the power supply CPU fail arc fault sensor Normally picked up drops out to signal an alarm condition OU...

Page 7: ...nput Configuration switches Primary PCB 7 9 11 13 15 17 19 21 Zone 1 Arc sensor input 1S30 Arc Fault Sensors Zone 2 Arc sensor input Zone 3 Arc sensor input Zone 4 Arc sensor input 6 8 Zone 1 Trip Zone 1 Trip Zone 2 Trip Zone 2 Trip 4 Common Trip Switch 1 Switch 2 Switch 3 Switch 4 BANK A BANK B BANK C 27 25 23 Fail Healthy Alarm common Signal processing and logic functions ON ON ON Arc sensor fau...

Page 8: ...aw out case ACCESSORIES SUPPLIED WITH EACH RELAY 1 x M4 self threading mounting screw kit P N 290 406 151 2 x M4 terminal screw kit 28 per kit P N 290 407 153 1 x Product Test Manual 1S30 ARC FAULT SENSORS Refer to the 1S30 Technical Bulletin for details Figure 11 1S30 Arc Fault Sensors Through panel mounting detector version depicted at left Front panel view of dual detector version depicted at r...

Page 9: ...e 1S25 product ordering code For maximum font size limit text for each alarm point to 1 line x 10 characters Text will be left justified Zone 1 Zone 2 Zone 3 Zone 4 Ordering Information ORDER CODE The order code determines the production build in the factory cannot be changed in the field Generate the required order code as follows e g 1S25 BA Order Code General Type 1 2 1S25 1 AUXILIARY SUPPLY RA...

Page 10: ...supplied in secure individual packing cardboard boxes with moulded styrene inserts suitable for recycling Each product packing box is labeled with the product part number customer name order details Design References The products components produced by RMS are based on many years of field experience since Relays Pty Ltd was formed in 1955 A large population of equipment is in service throughout Au...

Reviews: