ROA
: Relay operate angle for zero sequence directional feature. It is used to
differentiate an internal fault and an external fault based on measured zero sequence
current and neutral current.
CTFactorPri1
: A factor to allow a sensitive function also at multi-breaker arrangement
where the rating in the bay is much higher than the rated current of the transformer
winding. The stabilizing can then be high so an unnecessary high fault level can be
required. The setting is normally 1.0 but in multi-breaker arrangement the setting shall
be CT primary rating/
IBase
.
CTFactorPri2
: A factor to allow a sensitive function also at multi-breaker arrangement
where the rating in the bay is much higher than the rated current of the transformer
winding. The stabilizing can then be high so an unnecessary high fault level can be
required. The setting is normally 1.0 but in multi-breaker arrangement the setting shall
be CT primary rating/
IBase
.
CTFactorSec1
: See setting
CTFactorPri1
. Only difference is that
CTFactorSec1
is
related to W2 side.
CTFactorSec2
: See setting
CTFactorPri2.
Only difference is that
CTFactorSec2
is
related to W2 side.
7.4
Additional security logic for differential protection
LDRGFC (11)
GUID-0E064528-0E70-4FA1-87C7-581DADC1EB55 v2
7.4.1
Identification
GUID-3081E62B-3E96-4615-97B8-2CCA92752658 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Additional security logic for differential
protection
LDRGFC
-
11
7.4.2
Application
GUID-93AF4444-C7ED-4DF5-9379-176DF17AE22C v4
Additional security logic for differential protection LDRGFC (11) can help the security
of the protection especially when the communication system is in abnormal status or
for example when there is unspecified asymmetry in the communication link. It
reduces the probability for mal-operation of the protection. LDRGFC (11) is more
sensitive than the main protection logic to always release operation for all faults
detected by the differential function. LDRGFC (11) consists of four sub functions:
Section 7
1MRK 504 163-UUS A
Differential protection
184
Transformer protection RET670 2.2 ANSI
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...