For the
TripAngle
it is recommended to set this parameter to 90° to assure limited
stress for the circuit breaker.
In a power system it is desirable to split the system into predefined parts in case of pole
slip. The protection is therefore situated at lines where this predefined split shall take
place.
Normally the
N1Limit
is set to 1 so that the line will be tripped at the first pole slip.
If the line shall be tripped at all pole slip situations also the parameter
N2Limit
is set to
1. In other cases a larger number is recommended.
8.16.3.2
Setting example for generator application
SEMOD172162-90 v4
In case of out of step conditions this shall be checked if the pole slip centre is inside the
generator (zone 1) or if it is situated in the network (zone 2).
ZC
ZA
ZB
en07000017.vsd
IEC07000017 V1 EN-US
Figure 240:
Generator application of pole slip protection
If the apparent impedance crosses the impedance line ZB – ZA this is the detected
criterion of out of step conditions, see figure
.
Section 8
1MRK 504 163-UUS A
Impedance protection
476
Transformer protection RET670 2.2 ANSI
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...