connected to the disturbance function blocks A1RADR to A4RADR. The eight
first ones belong to the public range and the remaining ones to the private range.
21.5.2
Settings
M17109-116 v1
21.5.2.1
Settings for RS485 and optical serial communication
M17109-118 v12
General settings
SPA, DNP and IEC 60870-5-103 can be configured to operate on the SLM optical
serial port while DNP and IEC 60870-5-103 additionally can utilize the RS485 port. A
single protocol can be active on a given physical port at any time.
Two different areas in the HMI are used to configure the IEC 60870-5-103 protocol.
1. The port specific IEC 60870-5-103 protocol parameters are configured under:
Main menu/Configuration/Communication/Station Communication/
IEC60870-5-103/
•
<config-selector>
•
SlaveAddress
•
BaudRate
•
RevPolarity (optical channel only)
•
CycMeasRepTime
•
MasterTimeDomain
•
TimeSyncMode
•
EvalTimeAccuracy
•
EventRepMode
•
CmdMode
•
RepIntermediatePos
<config-selector> is:
•
“OPTICAL103:1” for the optical serial channel on the SLM
•
“RS485103:1” for the RS485 port
2. The protocol to activate on a physical port is selected under:
Main menu/Configuration/Communication/Station Communication/Port
configuration/
•
RS485 port
•
RS485PROT:1 (off, DNP, IEC103)
•
SLM optical serial port
•
PROTOCOL:1 (off, DNP, IEC103, SPA)
1MRK 504 163-UUS A
Section 21
Station communication
Transformer protection RET670 2.2 ANSI
945
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...