9.17.3.2
Voltage-restrained overcurrent protection for generator and step-up
transformer
GUID-263B960B-2280-461C-B455-F17B7D278F60 v8
An example of how to use VRPVOC (51V) function to provide voltage restrained
overcurrent protection for a generator is given below. Let us assume that the time
coordination study gives the following required settings:
•
Inverse Time Over Current IDMT curve: IEC very inverse, with multiplier k=1
•
Pickup current of 185% of generator rated current at rated generator voltage
•
Pickup current 25% of the original pickup current value for generator voltages
below 25% of rated voltage
To ensure proper operation of the function:
1. Set
Operation
to
Enabled
2. Set
GlobalBaseSel
to the right value in order to select the Global Base Values
Group with
VBase
and
IBase
equal to the rated phase-to-phase voltage and the
rated phase current of the generator.
3. Connect three-phase generator currents and voltages to VRPVOC (51V) in the
application configuration.
4. Select
Characterist
to match the type of overcurrent curves used in the network
IEC Very inv.
5. Set the multiplier
k
=
1
(default value).
6. Set
tDef_OC
=
0.00
s, in order to add no additional delay to the trip time defined
by the inverse time characteristic.
7. If required, set the minimum operating time for this curve by using the parameter
t_MinTripDelay
(default value 0.05 s).
8. Set
PickupCurr
to the value 185%.
9. Set
VDepMode
to
Slope
(default value).
10. Set
VDepFact
to the value 25% (default value).
11. Set
VHighLimit
to the value 100% (default value).
All other settings can be left at the default values.
9.17.3.3
Overcurrent protection with undervoltage seal-in
GUID-B58E1CD6-F9AE-4301-ABE7-90DBFC987D69 v6
To obtain this functionality, the IED application configuration shall include a logic in
accordance to figure
and, of course, the relevant three-phase generator currents and
voltages shall be connected to VRPVOC. Let us assume that, taking into account the
characteristic of the generator, the excitation system and the short circuit study, the
following settings are required:
Section 9
1MRK 504 163-UUS A
Current protection
610
Transformer protection RET670 2.2 ANSI
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...