The WEI function can be extended to trip also the breaker in the weak side. The trip is
achieved when one or more phase voltages are low during an echo function.
Together with the blocking teleprotection scheme some limitations apply:
•
Only the trip part of the function can be used together with the blocking scheme. It
is not possible to use the echo function to send the echo signal to the remote line
IED. The echo signal would block the operation of the distance protection at the
remote line end and in this way prevents the correct operation of a complete
protection scheme.
•
A separate direct intertrip channel must be arranged from remote end when a trip
or accelerated trip is given there. The intertrip receive signal is connected to input
CRL.
•
The WEI function shall be set to
OperationWEI
=
Echo&Trip
. The WEI function
block will then give phase selection and trip the local breaker.
16.4.3
Setting guidelines
SEMOD156555-1 v2
SEMOD156562-5 v4
The parameters for the current reversal and weak-end infeed logic for phase segregated
communication function (ZC1WPSCH) are set via the local HMI or PCM600.
Common base IED values for primary current (
IBase
), primary voltage (
UBase
) and
primary power (
SBase
) are set in Global base values for settings function
GBASVAL
.
GlobalBaseSel
: It is used to select a
GBASVAL
function for reference of base values.
Current reversal logic
Set
OperCurrRev
to
On
to activate the function.
Set
tDelayRev
timer at the maximum reset time for the communication equipment that
gives the carrier receive (CRLx) signal plus 30 ms. A minimum setting of
40 ms
is
recommended, typical
60 ms
.
A long
tDelayRev
setting increases security against unwanted tripping, but delay the
fault clearing in case of a fault developing from one line to involve the other one. The
probability of this type of fault is small. Therefore set
tDelayRev
with a good margin.
Set the pick-up delay
tPickUpRev
to <80% of the minimum sum of breaker operate
time + communication delay time, but with a minimum of
20 ms
.
Weak-end infeed logic
Set
OperationWEI
to
Echo
, to activate the weak-end infeed function with only echo
function.
Set
OperationWEI
to
Echo&Trip
to obtain echo with trip.
1MRK 504 163-UUS A
Section 16
Scheme communication
Transformer protection RET670 2.2 ANSI
831
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...