Capacitive
Inductive
200
400
600
800
1000
200
400
600
Q
(Mvar)
500
1000
1500
Power flow
(MW)
(T.L.)
(S.C.)
(T.L. + S.C.)
Transmission
Line
Series
Compensation
500 kV
500 km
k = 50 %
en06000589.vsd
IEC06000589 V1 EN-US
Figure 83:
Self-regulating effect of reactive power balance
Increase in power transfer
SEMOD168320-45 v2
The increase in power transfer capability as a function of the degree of compensation
for a transmission line can be explained by studying the circuit shown in figure
power transfer on the transmission line is given by the equation
( )
( )
(
)
A
B
A
B
Line
C
Line
C
V
V
sin
V
V
sin
P
X
X
X
1 K
d
d
×
×
×
×
=
=
-
× -
EQUATION1994-ANSI V1 EN-US
(Equation 55)
The compensation degree K
c
A
B
-jX
C
P
A
Q
A
P
B
Q
B
V
A
V
B
V
+jX
L
V
A
V
B
en06000590_ansi.vsd
D
d
ANSI06000590 V1 EN-US
Figure 84:
Transmission line with series capacitor
The effect on the power transfer when considering a constant angle difference (δ)
between the line ends is illustrated in figure
. Practical compensation degree runs
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
209
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...