Inverse time delay characteristic of the NS2PTOC (46I2) function is represented in the
equation
2
2
I t
K
=
, where the
K1
setting is adjustable over the range of
1
–
99
seconds.
A typical inverse time overcurrent curve is shown in Figure
Negative sequence inverse time characteristic
Negative sequence current
T
im
e d
el
ay
I2
tMax
tMin
IEC08000355-2-en.vsd
1
10
100
1000
10000
0.01
0.1
1
10
100
IEC08000355 V2 EN-US
Figure 293:
Inverse Time Delay characteristic, step 1
The example in figure
indicates that the protection function has a set minimum trip
time
t1Min
of 5 sec. The setting
t1Min
is freely settable and is used as a security
measure. This minimum setting assures appropriate coordination with for example line
protections. It is also possible to set the upper time limit,
t1Max
.
9.16.3.2
Pickup sensitivity
GUID-1D038486-7086-466F-A92F-30E1A47D0298 v3
The trip pickup levels Current
I2-1>
and
I2-2>
of NS2PTOC (46I2) are freely settable
over a range of 3 to 500 % of rated generator current
IBase
. The wide range of pickup
setting is required in order to be able to protect generators of different types and sizes.
After pickup, a certain hysteresis is used before resetting pickup levels. For both steps
the reset ratio is 0.97.
1MRK 504 163-UUS A
Section 9
Current protection
Transformer protection RET670 2.2 ANSI
605
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...