![ABB RELION RET670 Applications Manual Download Page 100](http://html.mh-extra.com/html/abb/relion-ret670/relion-ret670_applications-manual_4714100.webp)
Where:
1)
shows how to connect the secondary side of the open delta VT to one VT input on the IED.
+3Vo shall be connected to the IED
2)
is the TRM where this voltage input is located. It shall be noted that for this voltage input the
following setting values shall be entered:
3 6.6 11.43
VTprim
kV
=
×
=
EQUATION1923 V1 EN-US
(Equation 4)
110
sec 3
110
3
VT
V
= ×
=
EQUATION1924 V1 EN-US
(Equation 5)
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the ratio
of the entered values exactly corresponds to ratio of one individual open delta VT.
6.6
3 6.6
3
110
110
3
×
=
EQUATION1925 V1 EN-US
(Equation 6)
3)
shows that in this example the first three input channel of the preprocessing block is not
connected in SMT tool or ACT tool.
4)
shows the connection made in Signal Matrix Tool (SMT), Application configuration tool
(ACT), which connect this voltage input to the fourth input channel of the preprocessing
function block 5).
5)
is a Preprocessing block that has the task to digitally filter the connected analog input and
calculate:
•
fundamental frequency phasors for all four input channels
•
harmonic content for all four input channels
•
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for sequence
quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the configuration
tool. For this application most of the preprocessing settings can be left to the default values.
If frequency tracking and compensation is required (this feature is typically required only for
IEDs installed in the generating stations ) then the setting parameters
DFTReference shall
be set accordingly.
Section 4
1MRK 504 163-UUS A
Analog inputs
94
Transformer protection RET670 2.2 ANSI
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...