For a bus-section disconnector, these conditions from the A1 busbar section are valid:
189OPTR (bay 1/sect.A1)
S1DC_OP
VPS1_DC
EXDU_BB
en04000494_ansi.vsd
AND
189OPTR (bay n/sect.A1)
. . .
. . .
. . .
VP189TR (bay 1/sect.A1)
VP189TR (bay n/sect.A1)
EXDU_BB (bay 1/sect.A1)
EXDU_BB (bay n/sect.A1)
. . .
. . .
. . .
. . .
. . .
. . .
AND
AND
ANSI04000494 V1 EN-US
Figure 341:
Signals from any bays in section A1 to a bus-section disconnector
For a bus-section disconnector, these conditions from the A2 busbar section are valid:
en04000495_ansi.vsd
189OPTR (bay 1/sect.A2)
S2DC_OP
VPS2_DC
EXDU_BB
189OPTR (bay n/sect.A2)
. . .
. . .
. . .
VP189TR (bay 1/sect.A2)
VP189TR (bay n/sect.A2)
VPDCTR (A2/A3)
EXDU_BB (bay n/sect.A2)
. . .
. . .
. . .
. . .
. . .
. . .
AND
DCOPTR (A2/A3)
EXDU_BB (bay 1/sect.A2)
EXDU_DC (A2/A3)
AND
AND
ANSI04000495 V1 EN-US
Figure 342:
Signals from any bays in section A2 to a bus-section disconnector
For a bus-section disconnector, these conditions from the B1 busbar section are valid:
1MRK 504 163-UUS A
Section 15
Control
Transformer protection RET670 2.2 ANSI
739
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...