To provide an effective protection for the generator for external unbalanced conditions,
NS2PTOC (46I2) is able to directly measure the negative sequence current. NS2PTOC
(46I2) also have a time delay characteristic which matches the heating characteristic of
the generator I
2
2
t = K as defined in standard.
where:
I
2
is negative sequence current expressed in per unit of the rated generator current
t
is operating time in seconds
K
is a constant which depends of the generators size and design
A wide range of I
2
2
t settings is available, which provide the sensitivity and capability
necessary to detect and trip for negative sequence currents down to the continuous
capability of a generator.
A separate output is available as an alarm feature to warn the operator of a potentially
dangerous situation.
9.16.2.1
Features
GUID-9B139200-C5FD-4870-93FD-2EB16B206B25 v4
Negative-sequence time overcurrent protection NS2PTOC (46I2) is designed to
provide a reliable protection for generators of all types and sizes against the effect of
unbalanced system conditions.
The following features are available:
•
Two steps, independently adjustable, with separate tripping outputs.
•
Sensitive protection, capable of detecting and tripping for negative sequence
currents down to 3% of rated generator current with high accuracy.
•
Two time delay characteristics:
•
Definite time delay
•
Inverse time delay
•
The inverse time overcurrent characteristic matches
2
2
I t
K
=
capability curve of
the generators.
•
Wide range of settings for generator capability constant
K
is provided, from 1 to
99 seconds, as this constant may vary greatly with the type of generator.
•
Minimum trip time delay for inverse time characteristic, freely settable. This
setting assures appropriate coordination with, for example, line protections.
1MRK 504 163-UUS A
Section 9
Current protection
Transformer protection RET670 2.2 ANSI
601
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...