Line voltage drop compensation for parallel control
SEMOD159053-186 v3
The line voltage drop compensation for a single transformer is described in section
. The same principle is used for parallel control with the circulating
current method and with the master – follower method, except that the total load
current, I
L
, is used in the calculation instead of the individual transformer current. (See
figure
for details). The same values for the parameters
Rline
and
Xline
shall be set
in all IEDs in the same parallel group. There is no automatic change of these
parameters due to changes in the substation topology, thus they should be changed
manually if needed.
Avoidance of simultaneous tapping
SEMOD159053-189 v1
Avoidance of simultaneous tapping (operation with the circulating current
method)
SEMOD159053-191 v3
For some types of tap changers, especially older designs, an unexpected interruption of
the auxiliary voltage in the middle of a tap manoeuvre, can jam the tap changer. In
order not to expose more than one tap changer at a time, simultaneous tapping of
parallel transformers (regulated with the circulating current method) can be avoided.
This is done by setting parameter
OperSimTap
to
On
. Simultaneous tapping is then
avoided at the same time as tapping actions (in the long term) are distributed evenly
amongst the parallel transformers.
The algorithm in Automatic voltage control for tap changer, parallel control TR8ATCC
(90) will select the transformer with the greatest voltage deviation V
di
to tap first. That
transformer will then start timing, and after time delay
t1
the appropriate VRAISE or
VLOWER command will be initiated. If now further tapping is required to bring the
busbar voltage inside
VDeadbandInner
, the process will be repeated, and the
transformer with the then greatest value of V
di
amongst the remaining transformers in
the group will tap after a further time delay
t2
, and so on. This is made possible as the
calculation of I
cc
is cyclically updated with the most recent measured values. If two
transformers have equal magnitude of V
di
then there is a predetermined order
governing which one is going to tap first.
Avoidance of simultaneous tapping (operation with the master follower method)
SEMOD159053-197 v2
A time delay for the follower in relation to the command given from the master can be
set when the setting
MFMode
is
Follow Tap
that is, when the follower follows the tap
position (with or without an offset) of the master. The setting parameter
tAutoMSF
then
introduces a time delay on VRAISE/VLOWER commands individually for each
follower, and effectively this can be used to avoid simultaneous tapping.
Homing
SEMOD159053-200 v2
Homing (operation with the circulating current method)
SEMOD159053-205 v3
This function can be used with parallel operation of power transformers using the
circulating current method. It makes possible to keep a transformer energized from the
1MRK 504 163-UUS A
Section 15
Control
Transformer protection RET670 2.2 ANSI
771
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...