HMI is
Main menu/Configuration/Time/Synchronization
. The parameters are
categorized as Time Synchronization (TIMESYNCHGEN) and IRIG-B settings (IRIG-
B:1) in case that IRIG-B is used as the external time synchronization source.
TimeSynch
M11348-167 v15
When the source of the time synchronization is selected on the local HMI, the
parameter is called
TimeSynch
. The time synchronization source can also be set from
PCM600. The setting alternatives are:
FineSyncSource
which can have the following values:
•
Disabled
•
SPA
•
LON
•
BIN
(Binary Minute Pulse)
•
GPS
•
GPS+SPA
•
GPS+LON
•
GPS+BIN
•
SNTP
•
GPS+SNTP
•
IRIG-B
•
GPS+IRIG-B
•
PPS
CoarseSyncSrc
which can have the following values:
•
Disabled
•
SPA
•
LON
•
DNP
•
IEC 60870-5-103
The function input to be used for minute-pulse synchronization is called BININPUT.
For a description of the BININPUT settings, see the
Technical Manual
.
The system time can be set manually, either via the local HMI or via any of the
communication ports. The time synchronization fine tunes the clock (seconds and
milliseconds).
The parameter
SyncMaster
defines if the IED is a master, or not a master for time
synchronization within a Substation Automation System, for IEDs connected in a
communication network (IEC 61850-8-1). The
SyncMaster
can have the following
values:
Section 24
1MRK 504 163-UUS A
Basic IED functions
980
Transformer protection RET670 2.2 ANSI
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...