In practice, the setting of fault resistance for both phase-to-ground
RFPE
and phase-to-
phase
RFPP
should be as high as possible without interfering with the load impedance
in order to obtain reliable fault detection.
8.13.3
Series compensation in power systems
GUID-7F3BBF91-4A17-4B31-9828-F2757672C440 v2
The main purpose of series compensation in power systems is virtual reduction of line
reactance in order to enhance the power system stability and increase loadability of
transmission corridors. The principle is based on compensation of distributed line
reactance by insertion of series capacitor (SC). The generated reactive power provided
by the capacitor is continuously proportional to the square of the current flowing at the
same time through the compensated line and series capacitor. This means that the series
capacitor has a self-regulating effect. When the system loading increases, the reactive
power generated by series capacitors increases as well. The response of SCs is
automatic, instantaneous and continuous.
The main benefits of incorporating series capacitors in transmission lines are:
•
Steady state voltage regulation and raise of voltage collapse limit
•
Increase power transfer capability by raising the dynamic stability limit
•
Improved reactive power balance
•
Increase in power transfer capacity
•
Reduced costs of power transmission due to decreased investment costs for new
power lines
8.13.3.1
Steady state voltage regulation and increase of voltage collapse limit
GUID-0AB9B4B5-92DF-4A3B-9046-FC3A460DA658 v1
A series capacitor is capable of compensating the voltage drop of the series inductance
in a transmission line, as shown in figure
. During low loading, the system voltage
drop is lower and at the same time, the voltage drop on the series capacitor is lower.
When the loading increases and the voltage drop become larger, the contribution of the
series capacitor increases and therefore the system voltage at the receiving line end can
be regulated.
Series compensation also extends the region of voltage stability by reducing the
reactance of the line and consequently the SC is valuable for prevention of voltage
collapse. Figure
presents the voltage dependence at receiving bus B (as shown in
figure
) on line loading and compensation degree
K
C
, which is defined according to
. The effect of series compensation is in this particular case obvious and
self explanatory.
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
413
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...