LowVoltTap
: This setting is used to set the position number of tap changer at possible
minimum voltage.
GUID-E9EC48CC-08D6-498E-BFB7-6F40AD9436A7 v1
The following settings are required to perform the calculation of top oil temperature
using monthly model of ambient temperature when AMBVALID is low:
JanAmbTmp
: This setting is used to set the January month average ambient
temperature.
FebAmbTmp
: This setting is used to set the February month average ambient
temperature.
MarchAmbTmp
: This setting is used to set the March month average ambient
temperature.
AprilAmbTmp
: This setting is used to set the April month average ambient temperature.
MayAmbTmp
: This setting is used to set the May month average ambient temperature.
JuneAmbTmp
: This setting is used to set the June month average ambient temperature.
JulyAmbTmp
: This setting is used to set the July month average ambient temperature.
AugAmbTmp
: This setting is used to set the August month average ambient
temperature.
SepAmbTmp
: This setting is used to set the September month average ambient
temperature.
OctAmbTmp
: This setting is used to set the October month average ambient
temperature.
NovAmbTmp
: This setting is used to set the November month average ambient
temperature.
DecAmbTmp
: This setting is used to set the December month average ambient
temperature.
GUID-F6960AEE-E0F9-4675-B8F2-A5DD53B10FEA v1
The hot spot temperature calculation is done by estimating the temperature rise
between the hot spot and the top oil. This difference is due to stray losses, local oil
flows and additional paper on conductor. The function has the following settings
related to hot spot to top oil temperature gradient calculation.
HPTmpRiseW1
: This setting is used to set the hot spot temperature rise of winding 1
above ambient temperature in K (Kelvin).
HPTmpRiseW2
: This setting is used to set the hot spot temperature rise of winding 2
above ambient temperature in K (Kelvin).
Section 18
1MRK 504 163-UUS A
Monitoring
910
Transformer protection RET670 2.2 ANSI
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...