RetripMode
FunctionMode
Description
No CBPos Check
Current
re-trip is done without check of
current level
Contact
re-trip is done without check of
auxiliary contact position
Current/Contact
re-trip is done without check of
current level or auxiliary contact
position
BuTripMode
: Back-up trip mode is given to state sufficient current criteria to detect
failure to break. For
Current
operation
2 out of 4
means that at least two currents, of
the three-phase currents and the residual current, shall be high to indicate breaker
failure.
1 out of 3
means that at least one current of the three-phase currents shall be
high to indicate breaker failure.
1 out of 4
means that at least one current of the three-
phase currents or the residual current shall be high to indicate breaker failure. In most
applications
1 out of 3
is sufficient. For
Contact
operation means back-up trip is done
when circuit breaker is closed (breaker position is used).
Pickup_PH
: Current level for detection of breaker failure, set in % of
IBase
. This
parameter should be set so that faults with small fault current can be detected. The
setting can be chosen in accordance with the most sensitive protection function to start
the breaker failure protection. Typical setting is 10% of
IBase
.
Pickup_BlkCont
: If any contact based detection of breaker failure is used, this function
can be blocked if any phase current is larger than this setting level. If the
FunctionMode
is set
Current/Contact
breaker failure for high current faults are safely
detected by the current measurement function. To increase security the contact based
function should be disabled for high currents. The setting can be given within the range
5 – 200% of
IBase
.
Pickup_N
: Residual current level for detection of breaker failure set in % of
IBase
. In
high impedance grounded systems the residual current at phase- to-ground faults are
normally much smaller than the short circuit currents. In order to detect breaker failure
at single-phase-ground faults in these systems it is necessary to measure the residual
current separately. Also in effectively grounded systems the setting of the ground-fault
current protection can be chosen to relatively low current level. The
BuTripMode
is set
1 out of 4
. The current setting should be chosen in accordance to the setting of the
sensitive ground-fault protection. The setting can be given within the range 2 – 200 %
of
IBase
.
t1
: Time delay of the re-trip. The setting can be given within the range 0 – 60s in steps
of 0.001 s. Typical setting is 0 – 50ms.
1MRK 504 163-UUS A
Section 9
Current protection
Transformer protection RET670 2.2 ANSI
573
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...