Table 66:
General settings parameters for the Measurement function
Setting
Short Description
Selected
value
Comments
Operation
Operation Off/On
On
Function must be
On
PowAmpFact
Amplitude factor to scale power
calculations
1.000
It can be used during commissioning
to achieve higher measurement
accuracy. Typically no scaling is
required
PowAngComp
Angle compensation for phase
shift between measured I & U
0.0
It can be used during commissioning
to achieve higher measurement
accuracy. Typically no angle
compensation is required. As well
here required direction of P & Q
measurement is towards protected
object (as per IED internal default
direction)
Mode
Selection of measured current
and voltage
L1, L2, L3 All three phase-to-ground VT inputs
are available
k
Low pass filter coefficient for
power measurement, V and I
0.00
Typically no additional filtering is
required
VGenZeroDb
Zero point clamping in % of
Ubase
25
Set minimum voltage level to 25%.
Voltage below 25% will force S, P and
Q to zero.
IGenZeroDb
Zero point clamping in % of
Ibase
3
Set minimum current level to 3%.
Current below 3% will force S, P and
Q to zero.
VBase (set in
Global base)
Base setting for voltage level in
kV
400.00
Set rated OHL phase-to-phase
voltage
IBase (set in
Global base)
Base setting for current level in
A
1000
Set rated primary CT current used for
OHL
SBase (set in
Global base)
Base Setting for power base in
MVA
1000
Set based on rated Power
Table 67:
Settings parameters for level supervision
Setting
Short Description
Selected
value
Comments
PMin
Minimum value
-100
Minimum expected load
PMax
Minimum value
100
Maximum expected load
PZeroDb
Zero point clamping in 0.001% of
range
3000
Set zero point clamping to 60 MW
that is, 3% of 200 MW
PRepTyp
Reporting type
db
Select magnitude deadband
supervision
PDbRepInt
Cycl: Report interval (s), Db: In
0.001% of range, Int Db: In
0.001%s
2000
Set ±Δdb=40 MW that is, 2% (larger
changes than 40 MW will be reported)
Table continues on next page
1MRK 504 163-UUS A
Section 18
Monitoring
Transformer protection RET670 2.2 ANSI
871
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...