Power View 

Enhanced PDU 

 
 

- PS570A 
 

 

 

Installation and Operations Manual 

 

Summary of Contents for Power View PS570A

Page 1: ...Power View Enhanced PDU PS570A Installation and Operations Manual ...

Page 2: ...eritoneal dialysis systems neonatal ventilator incubators ventilators for adults or infants anesthesia ventilators infusion pumps and any other devices designated as critical by the U S FDA Compliance Units have been safety tested certified to the following standards USA and Canada to UL 1950 and CAN CSA 22 2 No 950 95 and European Union to EN60950 USA Notification Warning Changes or modifications...

Page 3: ...Overview 6 Safety Precautions 6 Mounting 7 Connecting to the Power Source 7 Connecting Devices 7 Connecting to the Power View 7 CHAPTER 3 OPERATIONS 9 Interfaces 10 HTML Interface 10 Command Line Interface 16 CHAPTER 4 APPENDICES 23 Appendix A Resetting to Factory Defaults 24 Appendix B Uploading Firmware 24 Appendix C Technical Specifications 25 Appendix D Product Registration and Support 26 ...

Page 4: ......

Page 5: ...AND BENEFITS 2 Communication Access Modes 2 Power Distribution Remote Management 2 Load and Environment Measurement 2 Outlet Grouping 2 User Interfaces and LEDs 2 Security 2 Automatic Timeout 2 TECHNICAL SUPPORT 3 QUICK START GUIDE 3 ...

Page 6: ...it without worry Use of the circuit is maximized while effectively allowing a 10 to 20 safety margin Outlet Grouping For operations across multiple attached devices or devices with multiple or redundant power supplies The Enhanced PDU s outlets may be included in one or more named groups of outlets Changes may then be applied to all outlets in the named group with one easy command sequence User In...

Page 7: ...ge number listed to the right For your network security Black Box strongly recommends the removal of the predefined user account prior to attachment to your network 1 Mount the Power View 6 2 Connect to the power source 7 3 Connect the devices to the Power View 7 4 Connect to the Power View 7 5 Configure the Power View 7 Login as the predefined Administrator admn admn 11 16 Configure the network s...

Page 8: ......

Page 9: ...STANDARD ACCESSORIES 6 ADDITIONAL REQUIRED ITEMS 6 EQUIPMENT OVERVIEW 6 SAFETY PRECAUTIONS 6 MOUNTING 7 CONNECTING TO THE POWER SOURCE 7 CONNECTING DEVICES 7 CONNECTING TO THE POWER VIEW 7 Console RS232 port 7 Ethernet port 7 ...

Page 10: ...ust be provided and must meet all applicable codes and regulations In North American protection must have a 10 000A interrupt capacity Le circuit spécialisé doit avoir un disjoncteur ou une protection de fusible Power Views ont été conçus sans disjoncteur général ni fusible pour éviter que cela devient un seul endroit de panne C est la responsabilité du client de fournir une protection adéquate po...

Page 11: ... électriques débranchez le cable électrique avant d ouvrir Immer Netzleitung auskuppeln vor den Aufmachen um elektrischen Schlag zu vermeiden Connecting to the Power View Console RS232 port The Power View is equipped with an RJ45 Console RS 232 port for attachment to a PC or networked terminal server See Data Connections in Appendix C Technical Specifications for more information on the Console RS...

Page 12: ......

Page 13: ...ut Feeds 12 Configuration 12 System 12 Network 12 Telnet HTTP 13 Outlets 13 Groups 13 Users 14 FTP 15 Tools 15 Restart 15 COMMAND LINE INTERFACE 16 Logging In 16 Operations Commands 17 Outlet Control 17 Administration Commands 19 System Administration 19 TCP IP Administration 19 Telnet Administration Commands 20 HTTP Administration Commands 20 FTP Administration 21 ...

Page 14: ...ional user accounts and then grant these users the right to view the status of and control power to specific outlets groups and ports Usernames may contain from 1 16 characters and are not case sensitive spaces are not allowed Passwords may contain up to 16 characters and are case sensitive HTML Interface The HTML interface is constructed of three major components the System Location bar the User ...

Page 15: ...as occurred Last Control State has been maintained On Wake On A power loss has occurred Wakeup State has been applied Off Wake Off A power loss has occurred Wakeup State has been applied On Wait Off Outlet state in transition Requery of outlet status required Off Wait On Outlet state in transition Requery of outlet status required On Error varies Error State Outlet should be off but current is sen...

Page 16: ...scriptive name and press Apply Creating a descriptive input feed name Click on the Input Feed Names link On the subsequent Input Feed Names page enter a descriptive name and press Apply Creating a descriptive outlet name Click on the Outlet Names link which will open the Outlets configuration page See Outlets on page 13 for additional information on creating descriptive outlet names Network The Ne...

Page 17: ...her level of security than the Basic method but at present is not supported by all browsers NOTE MD5 is known to be fully supported by Internet Explorer 5 0 Select Basic or MD5 from the Authentication drop down menu and press Apply Outlets The Outlets configuration page is used for assignment and or editing of outlet descriptive names and wakeup states Editing the outlet descriptive name Click on ...

Page 18: ...erial Pass Thru ports The administrator may also grant administrative privileges to other user accounts allowing the Power View to have more than one administrative level user NOTE You cannot remove administrative privileges from the Admn user unless another user has already been given administrative access level privileges created Click on the Edit link in the Action column for the associated use...

Page 19: ... test validates that the unit is able to contact and log onto the specified FTP server download the firmware file and verify that the firmware file is valid for this unit Press Test Tools The Tools section contains access to rebooting the unit uploading new firmware as well as resetting the unit to factory defaults This section is available to administrative level users only Restart Performing a w...

Page 20: ...trative privileges to use the administration commands The following tables list and briefly describe each command Operations Command Summary Command Description On Turns one or more outlets on Off Turns one or more outlets off Reboot Reboots one or more outlets Status Displays the on off status of one or more outlets Login Ends the current session and brings up the Username prompt Logout Ends a se...

Page 21: ...ts off At the Power View Enhanced PDU prompt type off followed by an outlet name and press Enter or Type off followed by a group name and press Enter or Type off all and press Enter Examples The following command turns off the outlet named FileServer_1 Power View Enhanced PDU off FileServer_1 Enter The following command turns off all outlets Power View Enhanced PDU off all Enter Rebooting outlets ...

Page 22: ... command displays the on off status of all accessible outlets Power View Enhanced PDU status Enter Outlet Outlet Outlet Control Outlet ID Name Status State Load AA1 DataServer_1 On On 5 0 Amps AA2 WebServer_1 On On 2 5 Amps AB1 FileServer_1 On On 9 5 Amps AB2 On On 0 0 Amps The following command displays the on off status for outlets in the group ServerGroup_1 Power View Enhanced PDU status Server...

Page 23: ...mpt type set ipaddress followed by the IP address and press Enter Example The following command sets the IP address to 12 34 56 78 Power View Enhanced PDU set ipaddress 12 34 56 78 Enter Setting the subnet mask The Set Subnet command sets the subnet mask for the network the Power View Enhanced PDU will be attached to To set the subnet mask At the Power View Enhanced PDU prompt type set subnet foll...

Page 24: ...ponds to requests on the default HTTP port number 80 This port number may be changed using the Set HTTP Port command To change the HTTP port At the Power View Enhanced PDU prompt type set http port followed by the port number and press Enter Example The following changes the HTTP port number to 2048 Power View Enhanced PDU set HTTP port 2048 Enter Setting the HTTP authentication method The Set HTT...

Page 25: ...peed 100 Mbps Duplex Half FTP Administration The following commands are used to configure the Power View Enhanced PDU for an FTP firmware upload See Appendix B Uploading Firmware for more information on initiating a FTP firmware upload Setting the FTP Host IP address The Set FTP Host command sets the FTP host IP address allowing for firmware file uploads To set the FTP Host IP address At the Power...

Page 26: ...e to be uploaded The FTP Filepath command sets the filepath for the firmware file to be uploaded To set the FTP filepath At the Power View Enhanced PDU prompt type set ftp filepath followed by the filepath and press Enter Example The following command sets the FTP filepath to ftp Powerview Power View Enhanced PDU set ftp filepath ftp Powerview Enter Displaying FTP configuration information The Sho...

Page 27: ...o factory defaults using the reset button 24 APPENDIX B UPLOADING FIRMWARE 24 To initiate an FTP upload session 24 To initiate an FTP upload session from the command line 24 APPENDIX C TECHNICAL SPECIFICATIONS 25 Models 25 Power Ratings 25 Physical Specifications 25 Data Connections 25 LED Indicators 25 APPENDIX D PRODUCT REGISTRATION AND SUPPORT 26 Technical Support 26 Troubleshooting 26 ...

Page 28: ...ppendix B Uploading Firmware You may upload new versions of firmware using File Transfer Protocol FTP This allows access to new firmware releases for firmware improvements and new features additions NOTE To begin an FTP upload session you must first configure the FTP Host address username password filename and filepath For information on configuring the FTP settings required for firmware upload se...

Page 29: ...50 2000 10 to 90 non condensing 10 to 90 non condensing cCSAus TUV GS1 0 to 50 000 ft 0 to 15 000 m 3 5 x 17 0 x 17 0 in PS570A 22 8 lbs 0 to 50 C 32 to 122 F 40 to 85 C 40 to 185 F 0 to 10 000 ft 0 to 3000 m Data Connections RS 232 port Enhanced PDUs are equipped standard with an RJ45 DTE RS 232c serial port This connector may be used for direct local access or from other serial devices such as a...

Page 30: ... do make a record of the history of the problem We will be able to provide more efficient and accurate assistance if you have a complete description including The model and serial number of the problem unit The nature and duration of the problem When the problem occurs Any particular application that when used appears to create the problem or make it worse Shipping and Packaging If you need to tra...

Page 31: ......

Page 32: ...order toll free 1 877 877 BBOX 1000 Park Drive technical support tel 1 724 46 5500 Lawrence PA 15055 fax 1 724 746 0746 USA www blackbox com info backbox com 301 0401 2 Rev A 013104 Black Box Corporation All rights reserved ...