X
c
is the reactance of the series capacitor
p is the maximum allowable reach for an under-reaching zone with respect to the sub-
harmonic swinging related to the resulting fundamental frequency reactance the zone is
not allowed to over-reach.
The degree of compensation C in figure
has to be interpreted as the relation
between series capacitor reactance X
C
and the total positive sequence reactance X1 to
the driving source to the fault. If only the line reactance is used the degree of
compensation will be too high and the zone 1 reach unnecessary reduced. The highest
degree of compensation will occur at three phase fault and therefore the calculation
need only to be performed for three phase faults.
The compensation degree in ground return path is different than in phases. It is for this
reason possible to calculate a compensation degree separately for the phase-to-phase
and three-phase faults on one side and for the single phase-to-ground fault loops on the
other side. Different settings of the reach for the ph-ph faults and ph-G loops makes it
possible to minimise the necessary decrease of the reach for different types of faults.
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
437
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...