17.1.2.4
Lock-out
M14828-18 v5
The SMPPTRC function block is provided with possibilities to initiate lock-out. The
lock-out can be set to only activate the block closing output CLLKOUT or initiate the
block closing output and also maintain the trip signal output TR3P (latched trip).
The lock-out can then be manually reset after checking the primary fault by activating
the input reset lock-out RSTLKOUT.
If external conditions are required to initiate a closing circuit lock-out but not to
lockout trip, this can be achieved by activating input SETLKOUT. The setting
AutoLock
=
Disabled
means that the internal trip will not activate lock-out so only
initiation of the input SETLKOUT will result in lock-out. This is normally the case for
overhead line protection where most faults are transient. Unsuccessful autoreclose and
back-up zone tripping can in such cases be connected to initiate lock-out by activating
the input SETLKOUT.
17.1.2.5
Example of directional data
GUID-08AC09AB-2B2F-4095-B06E-1171CF225869 v2
An example how to connect the directional data from different application functions to
the trip function is given below, see Figure
:
1MRK 504 163-UUS A
Section 17
Logic
Transformer protection RET670 2.2 ANSI
843
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...