1. Input CT channels on the transformer input modules.
2. General settings for the transformer differential protection where specific data
about protected power transformer shall be entered.
Finally the setting for the differential protection characteristic will be given for all
presented applications.
Example 1: Wye-delta connected power transformer without on-load
tap-changer
SEMOD167854-110 v5
Single line diagrams for two possible solutions for such type of power transformer with
all relevant application data are given in figure
.
CT 300/5
in Delta
(DAC)
CT 800/5
Wye
20.9 MVA
69/12.5 kV
YNd1
(YD
AC
)
CT 300/5
Wye
CT 800/5
Wye
20.9 MVA
69/12.5 kV
YNd1
(YD
AC
)
en06000554_ansi.vsd
ANSI06000554 V1 EN-US
Figure 50:
Two differential protection solutions for wye-delta connected power
transformer
For this particular power transformer the 69 kV side phase-to-ground no-load voltages
lead by 30 degrees the 12.5 kV side phase-to- ground no-load voltages. Thus when
external phase angle shift compensation is done by connecting main HV CTs in delta,
as shown in the right-hand side in figure
, it must be ensured that the HV currents
Section 7
1MRK 504 163-UUS A
Differential protection
148
Transformer protection RET670 2.2 ANSI
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...