SIRLevel
: The setting of the parameter
SIRLevel
is by default set to 10. This is a
suitable setting for applications with CVT to avoid transient overreach due to the CVT
dynamics. If magnetic voltage transformers are used, set
SIRLevel
to 15 the highest
level.
IMinOp
: The minimum operate current for the SIR measurement is by default set to
20% of
IBase
.
8.8
Faulty phase identification with load encroachment
FMPSPDIS (21)
SEMOD153819-1 v5
8.8.1
Identification
SEMOD155879-2 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Faulty phase identification with load
encroachment for mho
FMPSPDIS
S00346 V1 EN-US
21
8.8.2
Application
SEMOD154764-4 v6
The operation of transmission networks today is in many cases close to the stability
limit. Due to environmental considerations the rate of expansion and reinforcement of
the power system is reduced for example, difficulties to get permission to build new
power lines.
The ability to accurately and reliably classifying different types of fault so that single
pole tripping and autoreclosing can be used which plays an important roll in this
matter.
Faulty phase identification with load encroachment for mho (FMPSPDIS) function is
designed to accurately select the proper fault loop in the Distance protection function
dependent on the fault type.
The heavy load transfer that is common in many transmission networks may in some
cases be in opposite to the wanted fault resistance coverage. Therefore, FMPSPDIS has
an built-in algorithm for load encroachment, which gives the possibility to enlarge the
resistive setting of both the Phase selection with load encroachment and the measuring
zones without interfering with the load.
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
317
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...