Wearing of the tap changer contacts
SEMOD159053-376 v4
Two counters, ContactLife and NoOfOperations are available within the Tap changer
control and supervision function, 6 binary inputs TCMYLTC or 32 binary inputs
TCLYLTC (84). They can be used as a guide for maintenance of the tap changer
mechanism. The ContactLife counter represents the remaining number of operations
(decremental counter) at rated load.
ContactLife
ContactLife
n+1
n
Irated
Iload
a
æ
ö
=
- ç
÷
ç
÷
è
ø
EQUATION1873 V2 EN-US
(Equation 512)
where n is the number of operations and α is an adjustable setting parameter,
CLFactor
, with default value is set to 2. With this default setting an operation at rated
load (current measured on HV-side) decrements the ContactLife counter with 1.
The NoOfOperations counter simply counts the total number of operations
(incremental counter).
Both counters are stored in a non-volatile memory as well as, the times and dates of
their last reset. These dates are stored automatically when the command to reset the
counter is issued. It is therefore necessary to check that the IED internal time is correct
before these counters are reset. The counter value can be reset on the local HMI under
Main menu/Reset/Reset counters/TransformerTapControl(YLTC,84)/TCMYLTC:
1 or TCLYLTC:1/Reset Counter and ResetCLCounter
Both counters and their last reset dates are shown on the local HMI as service values
under
Main menu/Test/Function status/Control/TransformerTapControl(YLTC,
84)/TCMYLTC:x/TCLYLTC:x/CLCNT_VAL
and
Main menu/Test/Function status/
Control/TransformerTapControl (YLTC,84)/TCMYLTC:x/TCLYLTC:x/
CNT_VAL
15.4.3
Setting guidelines
SEMOD171503-1 v1
15.4.3.1
TR1ATCC or TR8ATCC general settings
SEMOD171501-4 v3
TrfId
: The transformer identity is used to identify transformer individuals in a parallel
group. Thus, transformers that can be part of the same parallel group must have unique
identities. Moreover, all transformers that communicate over the same horizontal
communication (GOOSE) must have unique identities.
Xr2
: The reactance of the transformer in primary ohms referred to the LV side.
Section 15
1MRK 504 163-UUS A
Control
790
Transformer protection RET670 2.2 ANSI
Application manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 48: ...42 ...
Page 64: ...58 ...
Page 74: ...68 ...
Page 104: ...98 ...
Page 194: ...188 ...
Page 518: ...512 ...
Page 618: ...612 ...
Page 648: ...642 ...
Page 666: ...660 ...
Page 672: ...666 ...
Page 682: ...676 ...
Page 844: ...838 ...
Page 868: ...862 ...
Page 956: ...950 ...
Page 964: ...958 ...
Page 1004: ...998 ...
Page 1014: ...1008 ...
Page 1015: ...1009 ...